Recommended lighting levels

Lux, UGR and Ra by type of space

Table of lighting levels by type of space

Typical maintained average illuminance values (Em) for indoor lighting, taken from standard EN 12464-1, together with the glare limit (UGR) and the minimum colour rendering (Ra). For sports facilities the values from EN 12193 are given. Click Calculate to take the value to the lighting calculator.

Space or taskEm (lx)Max. UGRMin. Ra
General areas
Corridors and circulation areas1002840
Stairs, escalators1002540
Dining rooms, canteens2002280
Rest rooms1002280
Toilets, changing rooms, bathrooms2002580
Sick bay, first aid rooms5001980
Plant rooms, switchboards2002560
Offices
Writing, reading, data processing5001980
Display screen workstations5001980
Meeting and conference rooms5001980
Technical drawing, CAD7501680
Reception3002280
Archives2002580
Industry, halls and workshops
Warehouses and stores1002560
Dispatch, packing, handling3002560
Assembly hall: coarse work3002580
Assembly hall: medium work5002280
Assembly hall: fine work7501980
Machine shop: general machining3002260
Winding of large coils3002580
Winding of medium coils5002280
Winding of small coils7501980
Electronics assembly and inspection10001680
Control rooms5001680
Covered car parks
Traffic lanes752540
Parking areas75–40
Entry and exit ramps (daytime)3002540
Entry and exit ramps (night-time)752540
Ticket offices and pay points3001980
Education
Classrooms3001980
Classrooms for evening and adult classes5001980
Board5001980
Laboratories, practical rooms5001980
Drawing rooms7501980
Retail
Sales area3002280
Tills5001980
Sports facilities (EN 12193, horizontal illuminance)
Football: training, recreational use (class III)75–20
Football: local competition (class II)200–60
Football: national competition (class I)500–60
Outdoor tennis: class III / II / I200 / 300 / 500–20 / 60 / 60
Sports hall: class III / II / I200 / 300 / 750–60
Homes (usual recommendations, no mandatory standard)
Living room, dining room150–300–80
Kitchen (worktop)300–500–80
Bedroom100–200–80
Bathroom (mirror)200–500–80
Home office5001980
Corridors100–80

Indicative values compiled from the tables of EN 12464-1 and EN 12193. The standard is revised periodically and in some cases allows the level to be raised because of the task conditions or the age of the users: for projects, always check the current edition.

What each column means

Frequently asked questions

How many lux does an office need?

500 lx in the writing, reading and display screen areas, with UGR ≤ 19. In corridors 100 lx is enough.

What lighting level does an industrial hall need?

It depends on the task: 100 lx if it is only storage, 300 lx for coarse work, 500 lx for medium assembly and 750 lx for fine or precision work.

And a car park?

75 lx in lanes and parking spaces; on the entry and exit ramps, 300 lx during the day (so the eyes can adapt when passing from outside to inside) and 75 lx at night.

How do I go from lux to number of luminaires?

With the lumen method: the lighting calculator gives you the number of luminaires and their layout from the room dimensions, the luminaire flux and these levels.