Illuminance at every point, isolux map and uniformity of an installation
The lumen method gives the average illuminance of a room, but not how the light is distributed. The point-by-point method calculates the lux at each point by adding what each luminaire contributes. This shows the dark areas, checks the uniformity and lets you light specific areas, such as a workstation, a sports court or a street.
The luminaires follow a symmetrical model distribution (cosⁿ) with the chosen beam angle; with the manufacturer's real curve the result may vary somewhat. Reflected light is estimated as uniform throughout the room, which is reasonable in rooms of normal proportions.
For a point luminaire at a height \(h\) above the calculation plane, a point at a horizontal distance \(r\) from its vertical receives the light at an angle \(\gamma\) from the vertical. The real distance is \(d = h/\cos\gamma\) and the light arrives tilted, so:
\(I(C,\gamma)\) is read from the luminaire's polar curve, in cd/klm, and multiplied by its flux in klm. The cube of the cosine makes the illuminance drop quickly as you move away: at 45° (\(r = h\)) only 35 % of what would arrive vertically with the same intensity remains.
On a vertical plane (a whiteboard, a shelf, a façade or a person's face) facing the luminaire:
The total illuminance at a point is the sum of what each luminaire contributes, plus the light reflected by the ceiling, walls and floor. A simple estimate of this indirect component, assuming it is uniform, is:
where \(\bar\rho\) is the average reflectance of the room weighted by area and \(S_{tot}\) the total area of ceiling, walls and floor. With light colours the reflected component can be a third of the total illuminance; with dark colours, almost nothing. More details in reflectance factors.
Uniformity \(U_0 = E_{min}/E_m\) shows whether the light is well distributed. EN 12464-1 normally requires \(U_0 \ge 0.6\) in the task area (0.4 for some undemanding tasks, 0.7 for very demanding ones) and lower values in the surroundings. Typical causes of poor uniformity are luminaires too far apart for their beam or too far from the walls. As a guide, the spacing between luminaires should not exceed about 1.5 times the height above the working plane, and the distance to the wall half that.
In practice the minimum illuminance is usually in the corners. The standard allows a 0.5 m perimeter band to be excluded from the calculation when there are no workstations against the wall; the calculator considers the whole room, so the result is somewhat pessimistic.
Below the luminaire (\(\gamma = 0\)):
1.5 m from the vertical, if the curve gives 180 cd/klm at that angle:
| Method | Gives | Suitable for |
|---|---|---|
| Lumen method | Average illuminance and number of luminaires | Pre-sizing the general lighting of an interior |
| Point by point | Lux at each point, minimums, uniformity | Checking uniformity, lighting specific areas, outdoor and road lighting, emergency lighting |
| Software (DIALux, Relux) | All of the above with exact interreflections, UGR, daylight | Complete projects and compliance documentation |
Related: photometric diagrams, lumen method, reflectance factors and lighting levels.