Enter the room dimensions, the lighting level you need and the luminaire data. The calculator gives the number of
luminaires, how to arrange them, the lux you will achieve, the power per square metre and the VEEI.
Luminaires needed–
Layout–
Illuminance achieved–
Room index (K)–
Utilisation factor–
Installed power–
VEEI–W/m² per 100 lx
Detailed calculation
How to calculate the lighting of a room
1. The lumen method
This is the classic method for general indoor lighting. It starts from the fact that the average illuminance is the useful flux reaching the
working plane divided by its area:
\(E_m\): maintained average illuminance (lx). \(S\): area (m²). \(\Phi\): flux of each luminaire (lm).
\(C_u\), utilisation factor: the part of the flux that reaches the working plane. It depends on the luminaire, the room geometry and the reflectances.
\(F_m\), maintenance factor: loss of flux due to ageing and dirt (0.6–0.8).
2. Room index
\[ K = \frac{L \cdot A}{h \cdot (L + A)} \]
where \(h\) is the height of the luminaire above the working plane. Low, wide rooms (large K) make better use of the light: more flux reaches
the floor and less is lost on the walls. The manufacturer gives the utilisation factor in a table according to K and the reflectances; the calculator uses
an average table for direct-distribution luminaires if you do not know it.
Solved example: 10 × 6 m office
Ceiling at 2.8 m, desks at 0.85 m, 3600 lm 36 W LED panels, 500 lx, clean room (\(F_m = 0.8\)), light colours.
Arranged in 4 × 4, at 2.5 m along the long side and 1.5 m along the short side. With 16 luminaires you get about 531 lx, with
576 W (9.6 W/m²) and a VEEI of 1.81.
3. Layout and checks
Spacing: the distance between luminaires should not exceed 1.0–1.5 times the height \(h\), and to the walls, half that spacing.
Uniformity: the method gives an average value. To check uniformity and glare (UGR), use a program such as DIALux with the luminaire files.
VEEI: in Spain, CTE DB HE 3 limits the energy efficiency value of the installation according to the use of the room
(for example, 3.0 W/m² per 100 lx in administrative areas). Check the current table for your case and your local regulations.