Lighting calculation

Lumen method: number of luminaires, lux and W/m²

Lighting calculator using the lumen method

Enter the room dimensions, the lighting level you need and the luminaire data. The calculator gives the number of luminaires, how to arrange them, the lux you will achieve, the power per square metre and the VEEI.

Room
m
m
m
m
0.85 m for desks; 0 m in corridors and warehouses
m
0 if surface-mounted or recessed
Lighting level
Luminaire
lm
Typical 60×60 LED panel: 3000–4000 lm
W
Empty: estimated from the room index. The manufacturer's value is better

How to calculate the lighting of a room

1. The lumen method

This is the classic method for general indoor lighting. It starts from the fact that the average illuminance is the useful flux reaching the working plane divided by its area:

\[ E_m = \frac{N \cdot \Phi \cdot C_u \cdot F_m}{S} \quad\Rightarrow\quad N = \frac{E_m \cdot S}{\Phi \cdot C_u \cdot F_m} \]

2. Room index

\[ K = \frac{L \cdot A}{h \cdot (L + A)} \]

where \(h\) is the height of the luminaire above the working plane. Low, wide rooms (large K) make better use of the light: more flux reaches the floor and less is lost on the walls. The manufacturer gives the utilisation factor in a table according to K and the reflectances; the calculator uses an average table for direct-distribution luminaires if you do not know it.

Solved example: 10 × 6 m office

Ceiling at 2.8 m, desks at 0.85 m, 3600 lm 36 W LED panels, 500 lx, clean room (\(F_m = 0.8\)), light colours.

\[ h = 2.8 - 0.85 = 1.95\ \text{m} \]\[ K = \frac{10 \cdot 6}{1.95 \cdot 16} = 1.92 \;\Rightarrow\; C_u \approx 0.69 \]
\[ N = \frac{500 \cdot 60}{3600 \cdot 0.69 \cdot 0.8} = 15.1 \;\Rightarrow\; 16\ \text{luminaires} \]

Arranged in 4 × 4, at 2.5 m along the long side and 1.5 m along the short side. With 16 luminaires you get about 531 lx, with 576 W (9.6 W/m²) and a VEEI of 1.81.

3. Layout and checks