VEEI, power density (W/m²) and consumption according to CTE DB HE 3
Limits from tables 3.1-HE3 and 3.2-HE3 of the Spanish Technical Building Code (DB HE, 2019 version and later amendments). They are a guide: for a project, always check the current text published in the Spanish Official Gazette (BOE).
The energy efficiency value of the installation (VEEI, from the Spanish valor de eficiencia energética de la instalación) states how many watts per square metre are needed for every 100 lux. The lower it is, the more efficient the installation: it combines in a single figure the efficacy of the lamps, the efficiency of the luminaires and how well the light is used in the room.
Comparing only W/m² would be unfair: a laboratory at 750 lx needs more power than a corridor at 100 lx. Dividing by the lux makes VEEI measure efficiency regardless of the lighting level.
Section HE 3 of the Basic Document on Energy Saving requires that the VEEI of each area does not exceed the limit in table 3.1-HE3, and that the total installed power per area does not exceed that in table 3.2-HE3.
| Room use | VEEI limit |
|---|---|
| Administrative in general; station platforms; exhibition or trade fair halls | 3.0 |
| Diagnostic rooms; classrooms and laboratories | 3.5 |
| Hospital wards; unlisted spaces; common areas; storerooms, archives, plant rooms and kitchens; car parks; sports areas | 4.0 |
| Transport stations; supermarkets, hypermarkets and department stores; libraries, museums and art galleries | 5.0 |
| Common areas in non-residential buildings; shopping centres (excluding shops) | 6.0 |
| Hospitality and restaurants; religious; assembly halls, auditoriums, meeting and conference rooms; shops and small retail | 8.0 |
| Hotel rooms, hostels, etc. | 10.0 |
| Rooms with a lighting level above 600 lx | 2.5 |
| Maximum installed power | W/m² |
|---|---|
| Car parks | 5 |
| Other uses with average illuminance up to 600 lx | 10 |
| Other uses with average illuminance above 600 lx | 25 |
In addition, each area must have manual on/off switching (the distribution board is not enough) and centralised time-scheduled switching. In areas of occasional use, such as toilets, corridors, stairs or car parks, the schedule can be replaced by presence detectors or timed push buttons. Luminaires less than 5 m from windows or under rooflights must be dimmed automatically according to daylight when the room receives enough outside light, except in some uses such as hotel or hospital rooms and small shops.
The requirements apply to new buildings and to refurbishments in which the lighting installation is renewed. Among other exceptions, the interiors of dwellings and protected buildings are excluded when complying would alter their character.
It meets the VEEI for administrative use and stays below the maximum power of 10 W/m². With the old 4 × 18 W fluorescent luminaires, which draw about 70 W with their ballast, the same office would exceed 1100 W and the VEEI would go above 3.7: it would not comply.
VEEI assesses installed power. The EN 15193 standard defines another indicator, LENI (Lighting Energy Numeric Indicator), which measures the energy consumed per square metre per year (kWh/m²·year) and takes into account hours of use, occupancy, daylight and control systems. It is the one used in energy certification and in schemes such as BREEAM or LEED.
Related: lighting calculation, lighting levels, lux and lumen converter and voltage drop.