Star, delta and zigzag, the clock number and which transformers can be paralleled
Each side of a three-phase transformer has three windings, one per limb, connected in one of these three ways:
| Connection | Voltage across each winding | Current in each winding | Neutral |
|---|---|---|---|
| Star | \(U_L/\sqrt3\) | \(I_L\) | Yes |
| Delta | \(U_L\) | \(I_L/\sqrt3\) | No |
| Zigzag | \(U_L/3\) across each half-winding | \(I_L\) | Yes |
\(U_L\) and \(I_L\) are the line-to-line voltage and the line current. In a zigzag the two half-windings of a phase are 60° apart and their sum is \(\sqrt3\) times each one; for the same voltage it needs 15.5 % more turns than a star (\(2/\sqrt3 = 1.155\)).
The voltage ratio is the ratio of line voltages, \(m = U_{1L}/U_{2L}\), but the turns ratio depends on the connections:
The designation, according to IEC 60076-1, combines the HV connection in capitals (Y, D, Z), the LV connection in lower case (y, d, z), an N or n if the neutral is brought out, and the clock number. For example:
Terminals are marked 1U, 1V, 1W on the HV side and 2U, 2V, 2W on the LV side, with 1N or 2N for the neutral. The ends of each winding are 1U1 and 1U2, 2U1 and 2U2… Older nameplates use A, B, C and a, b, c.
LV voltages are not always in phase with HV voltages: depending on the connections, they lag by a multiple of 30°. The clock number says how many: the 1U voltage is drawn at 12 o'clock and the 2U voltage falls on the hour given by the number.
Dyn11 has the LV lagging by 330°, which is the same as leading by 30°; Dyn5, lagging by 150°. Delta and zigzag shift 30° with respect to star, so Yy, Dd and Dz give even numbers, and Dy, Yd and Yz odd ones. Reversing the ends of the LV windings adds 6 (180°): Yy0 becomes Yy6.
| Number | Phase shift | Standard groups |
|---|---|---|
| 0 | 0° | Yy0, Dd0, Dz0 |
| 6 | 180° | Yy6, Dd6, Dz6 |
| 5 | 150° | Dy5, Yd5, Yz5 |
| 11 | 330° | Dy11, Yd11, Yz11 |
| 1 and 7 | 30° and 210° | Dy1, Yd1, Yz1 · Dy7, Yd7, Yz7 |
| 2, 4, 8 and 10 | 60° to 300° | Dd2, Dd4, Dd8, Dd10 · Dz2, Dz4, Dz8, Dz10 |
The first four are the usual ones. In practice almost all distribution transformers are Dyn11, Dyn5, Yyn0 or Yzn11.
Choose the connections and the clock number: the connection diagram is drawn, with a dot at the start of each winding, together with the clock diagram, showing the HV triangle (1U at 12) and the LV one. Below are the voltages to measure in the test of section 7.
| Group | Use | Why |
|---|---|---|
| Dyn11 (or Dyn5) | LV distribution, the most common | The neutral can carry fully unbalanced load; the HV delta traps third harmonics and spreads the unbalance over the three phases of the network. |
| Yyn0 | Small distribution transformers, older units | Cheap, with star-connected HV insulation, but the LV neutral can only take little load (usually limited to 10 % of rated): with single-phase load the zero-sequence flux shifts the neutral. For more load it needs a delta tertiary. |
| Yzn11 (or Yzn5) | Small rural distribution with a lot of single-phase load | The zigzag spreads the load of each phase over two limbs and the neutral can take full load, at the cost of 15.5 % more LV copper. |
| YNd11 (or YNd5) | Generator step-up and network transformers | Delta on the generator side; HV neutral for earthing the network. |
| Dd0 | Industry without neutral | If one unit of a bank of three single-phase transformers fails, it can keep running in open delta (V-V) with 57.7 % of the power. |
| Yd and Dy for rectifiers | 12-pulse rectifiers | Two secondaries 30° apart (one in star and one in delta) cancel the 5th and 7th harmonics. |
The neutral loading percentages are usual indicative values; the manufacturer gives those of each transformer.
To connect two or more three-phase transformers in parallel, HV to HV and LV to LV, these conditions must be met:
Each transformer takes a share of the load proportional to its rating divided by its short-circuit voltage:
If the ratios differ, a current circulates between the two transformers that only produces heat. With equal ratings, as a percentage of rated current:
With the neutrals joined, the voltage between two corresponding terminals of transformers with a phase difference \(\delta\) is:
With 230 V phase-to-neutral, 30° of difference (Dyn11 with Yyn0) gives 119 V and 180° (Yy0 with Yy6), 460 V. Before closing the paralleling breaker, measure with a voltmeter between each pair of corresponding terminals: it must read almost 0 V. The phase sequence is checked with a phase rotation meter. The single-phase case is in connecting transformers in parallel.
When the nameplate cannot be read or it is unclear how a rewound transformer was connected, the clock number can be checked without special instruments:
Each group gives a different set of voltages. If they do not match, try other clock numbers in the explorer until one fits. The voltmeter must read low voltages well, because the LV ones are small: with 400 V on a 20,000 / 420 V transformer, the LV side gives 8.4 V.
Related: transformer fundamentals · transformer analysis · single-phase transformers in parallel · delta-star transformation · harmonics