EN

Star/delta transformation

Convert a circuit from one type to the other to make analysis easier

Delta–star (Δ–Y) transformation

Convert three resistors connected in delta (Δ) into their star (Y) equivalent, or vice versa. It is the key tool for simplifying circuits that cannot be solved with series and parallel combinations alone, such as resistor bridges or three-phase loads.

RAB RCA RBC A B C
Delta (Δ)
RA RB RC A B C N
Star (Y)

Equivalent star

RA–
RB–
RC–

What is the delta–star transformation for?

Many circuits can be simplified by combining resistors in series or in parallel, but in some configurations no resistor is in series or in parallel with another. The typical example is the unbalanced Wheatstone bridge. In those cases, replacing a delta with its equivalent star (or vice versa) untangles the network and lets you keep simplifying.

The two configurations are equivalent when, measured between any pair of nodes (A–B, B–C or C–A), they show the same resistance. From the outside, the rest of the circuit cannot tell the difference. What changes are the internal currents and voltages of each resistor.

This transformation is also known as Kennelly's theorem or the Δ–Y, π–T or Pi–Tee transformation.

Formulas: delta to star (Δ → Y)

Each star resistor equals the product of the two delta resistors touching that node, divided by the sum of all three:

RA = RAB · RCA / (RAB + RBC + RCA)
RB = RAB · RBC / (RAB + RBC + RCA)
RC = RBC · RCA / (RAB + RBC + RCA)

Formulas: star to delta (Y → Δ)

Each delta resistor equals the sum of the star products taken two at a time, divided by the opposite star resistor:

RAB = (RA·RB + RB·RC + RC·RA) / RC
RBC = (RA·RB + RB·RC + RC·RA) / RA
RCA = (RA·RB + RB·RC + RC·RA) / RB

Balanced case

If the three resistors are equal, the formulas reduce to a very simple relationship:

RY = RΔ / 3 RΔ = 3 · RY

This is the usual situation in balanced three-phase loads, such as the three phases of a motor or of an industrial heating element.

Quick rule to remember them

ConversionNumeratorDenominator
Δ → YProduct of the two delta resistors adjacent to the nodeSum of the three delta resistors
Y → ΔSum of the star products taken two at a timeStar resistor opposite the side

Worked example

A delta with RAB = 10 Ω, RBC = 20 Ω and RCA = 30 Ω. The sum is 60 Ω, so:

Reverse check: the sum of products is 5·3.33 + 3.33·10 + 10·5 = 100, therefore RAB = 100 / 10 = 10 Ω, RBC = 100 / 5 = 20 Ω and RCA = 100 / 3.33 = 30 Ω. The original values are recovered. You can check it with the calculator above.

Relation to star–delta motor starting

This transformation should not be confused with star–delta starting. In star–delta starting the circuit is not replaced by an equivalent one: the same motor windings are reconnected. When the windings are switched from delta to star, each one receives a voltage √3 times lower, so the line current and the starting torque are reduced to one third. That same factor of 3 appears in the balanced case: a star-connected load draws one third of what the same load draws when connected in delta.

Does it also work for impedances?

Yes. The same formulas apply to AC impedances (resistors, inductors and capacitors), using complex numbers. This calculator works with resistances, which is the most common case in DC exercises and resistive loads.

Approximate calculation tool for study and checking. Verify the results before using them in a project.

Delta–star with impedances (complex numbers)

In AC, loads are not just resistances: they have an inductive or capacitive part. This calculator applies the same transformation to complex impedances. You can enter them in rectangular (R + jX) or polar (|Z| ∠ θ) form, and the result is given in both forms.

Input format:

Equivalent star

Rectangular and polar form

An impedance can be written in two equivalent ways:

To convert between them:

|Z| = √(R² + X²) θ = arctan(X / R)
R = |Z| · cos θ X = |Z| · sin θ

Sums are easier in rectangular form (real and imaginary parts are added separately). Products and quotients are easier in polar form: the magnitudes are multiplied or divided and the angles are added or subtracted.

(|Z₁| ∠ θ₁) · (|Z₂| ∠ θ₂) = |Z₁|·|Z₂| ∠ (θ₁ + θ₂)
(|Z₁| ∠ θ₁) / (|Z₂| ∠ θ₂) = |Z₁|/|Z₂| ∠ (θ₁ − θ₂)

Formulas with impedances

They are the same as with resistances, using complex numbers:

Δ → Y: ZA = ZAB·ZCA / ΣZΔ ZB = ZAB·ZBC / ΣZΔ ZC = ZBC·ZCA / ΣZΔ
Y → Δ: ZAB = P / ZC ZBC = P / ZA ZCA = P / ZB, with P = ZA·ZB + ZB·ZC + ZC·ZA

In the balanced case ZY = ZΔ / 3 still holds: the magnitude is divided by three and the angle does not change. That is why a balanced three-phase load has the same power factor whether it is connected in star or in delta.

Worked example

A delta with ZAB = 6 + j8 Ω (inductive), ZBC = 10 Ω (resistive) and ZCA = −j10 Ω (capacitive). They all have a magnitude of 10 Ω, but different angles: 53.13°, 0° and −90°.

Note that ZA turns out capacitive even though the delta contains an inductor: with complex impedances, each star branch combines the effect of the two delta branches touching its node.

A special case: resonance

If the delta reactances cancel each other out so that the sum ZAB + ZBC + ZCA is zero (for example j10, j10 and −j20 Ω), the formulas divide by zero: that delta is resonant and has no equivalent star. The calculator will warn you if this happens.

Approximate calculation tool for study and checking. Verify the results before using them in a project.