Open-circuit and short-circuit tests, equivalent circuit, voltage drop, efficiency and short circuit
In an ideal transformer the voltage is transformed by the turns ratio \(m = U_1/U_2\) and there are no losses. The real transformer needs a current to magnetise the core, loses power in the iron (hysteresis and eddy currents) and in the copper of the windings, and has leakage fluxes that cause voltage drops. All of this is captured in the approximate equivalent circuit, with the secondary referred to the primary:
For a three-phase transformer the equivalent star is used: phase voltages \(U/\sqrt3\) and power \(S/3\) per phase.
One winding (usually the low-voltage one) is fed at its rated voltage with the other open. The power \(P_0\) and current \(I_0\) are measured. Since the current is very small, copper losses are negligible and \(P_0\) is the iron loss, which is practically the same at any load.
With one winding short-circuited, the voltage on the other is raised until rated current flows. That voltage is small (a few percent of rated), so the flux and the iron losses are negligible and \(P_{cc}\) is the copper loss at full load.
The short-circuit voltage \(u_{cc}\) appears on the nameplate and sets the current of a bolted short circuit at the secondary terminals:
With a load factor \(C = I/I_n\) and a power factor \(\cos\varphi\), the relative voltage drop is (Kapp approximation with a second-order term):
\(\sin\varphi\) is positive for inductive loads and negative for capacitive ones. With a capacitive load the drop can be negative: the secondary voltage rises above the no-load voltage.
Iron losses are fixed and copper losses grow with the square of the load. Efficiency is highest when the two are equal. Distribution transformers, which spend many hours lightly loaded, are designed with low no-load losses so that this maximum falls at around 40 % or 50 % load.
P₀ = 900 W, Pcc = 6500 W, ucc = 4 %, at 75 % load and cos φ = 0.85 inductive.
The rated secondary current is \(630\,000/(\sqrt3 \cdot 420) = 866\) A and the short-circuit current at the terminals is 25 times higher: about 21.7 kA.