Connecting Transformers in Parallel

Introduction

Sometimes two or more transformers need to be connected in parallel because a single one cannot supply the required power. This may look simple, but certain precautions are needed; otherwise the loads may be unbalanced or one transformer may even draw energy from the other. To avoid this, check that:

Single-phase transformers

If the transformers meet the rules above, we can connect them. If they come from the same manufacturer and share the same characteristics, we can be almost 100% sure that each terminal of one transformer can be connected to the matching terminal of the other. Even so, it is advisable to check before making the final connection.

The figure shows two single-phase transformers connected in parallel. First, energise both primary windings. Then connect the secondary of T1 to the output line (preferably with no loads connected), and fit a switch M and a voltmeter on the output of T2. When M is closed, the voltmeter will read 0 V if the connection is correct, as follows from the symbols used. If not, the voltmeter will show a voltage, exactly the secondary voltage, which means the connection is wrong and the leads of one of the secondaries must be swapped.

For thermal protection, it is good practice to protect each transformer individually, at least on the secondary side, setting the protection current carefully: no more than 10% above the rated current. Since the transformers are in parallel, when one protection trips the other transformer automatically takes the whole load, and because it is properly protected its own protection will also trip, preventing further damage.

⚠ Poor protection of a transformer is dangerous: if, out of carelessness or to save money, it is protected well above its capacity, an overload or short circuit can easily start a fire.