Why they appear, what problems they cause and how they are measured: THD, K-factor and neutral current
The grid is designed for sinusoidal voltages and currents at 50 Hz (or 60 Hz). When a load draws a current that is not a sine wave, that distorted waveform can be broken down (Fourier series) into a sine wave at the grid frequency, the fundamental, plus other sine waves at integer multiples of it: the harmonics. The harmonic of order \(h\) has frequency \(h \cdot f_1\): on a 50 Hz grid the 3rd is at 150 Hz, the 5th at 250 Hz…
The total RMS value is the square root of the sum of the squares: with a sinusoidal voltage the harmonics do no useful work, but they do increase the RMS current and, with it, the \(R\,I^2\) losses. If the waveform is symmetrical about the axis (the normal case in steady state), even harmonics are negligible and only the odd ones remain.
They are produced by non-linear loads: those whose current is not proportional to the voltage. Almost always this is electronics that rectifies the grid voltage and smooths it with a capacitor, which only recharges at the peaks of the sine wave. The current then arrives in narrow pulses with a high harmonic content.
| Load | Dominant harmonics | Why |
|---|---|---|
| Single-phase switch-mode power supplies: computers, chargers, TVs, LED drivers | 3rd, 5th, 7th, 9th… | Rectifier with capacitor: current pulses at the voltage peak |
| Variable frequency drives and 6-pulse three-phase rectifiers | 5th, 7th, 11th, 13th… (\(h = 6k \pm 1\)) | Diode or thyristor bridge: each phase conducts in 120° blocks |
| 12-pulse rectifiers | 11th, 13th, 23rd, 25th… (\(h = 12k \pm 1\)) | Two bridges shifted by 30° that cancel the 5th and 7th |
| UPS, battery chargers and electric vehicle chargers | Depends on the input stage | Rectifier; equipment with active power factor correction (PFC) generates very little |
| Arc furnaces, welding | Broad spectrum, including even harmonics and interharmonics | The arc is a highly variable resistance |
| Saturated transformers and reactors | 3rd and 5th | The magnetising current is not sinusoidal when the core saturates |
Current harmonics belong to the load; the grid only "carries" them. But as they flow through the grid impedance (transformer and cables) they cause voltage drops at those frequencies and distort the voltage as well, which is what every other consumer receives.
In a three-phase system with neutral and balanced loads, the fundamental currents of the three phases cancel in the neutral. Harmonics that are multiples of 3 (3rd, 9th, 15th…), however, are in phase in all three phases and add up: with many switch-mode power supplies, the neutral current can exceed the phase current.
| Sequence | Orders | Effect |
|---|---|---|
| Positive (+) | 1, 4, 7, 10, 13… | Rotate like the fundamental: they cause heating |
| Negative (−) | 2, 5, 8, 11, 14… | In motors they create a braking torque and extra heating |
| Zero (0) | 3, 6, 9, 12, 15… | They add up in the neutral; in a delta winding they circulate inside it |
Total harmonic distortion (THD) is usually given relative to the fundamental (\(THD_F\), the one used by analysers and standards). With heavy distortion the difference from \(THD_R\) is large: 100 % \(THD_F\) is only 71 % \(THD_R\).
The true power factor is the product of the displacement factor (\(\cos\varphi_1\), that of the fundamental) and the distortion factor (assuming a sinusoidal voltage). The crest factor of a sine wave is \(\sqrt 2 \approx 1.41\); switch-mode supplies reach 2.5 or 3. The K-factor (UL 1561) measures the additional heating caused by eddy currents in a transformer: it is 1 with sinusoidal current, and transformers are built for K = 4, 13, 20…
Reference limits (check the current standard): EN 50160 sets a maximum THD of 8 % for the public grid voltage; current emission from equipment is limited by IEC 61000-3-2 (up to 16 A per phase) and IEC 61000-3-12 (16 to 75 A); IEEE 519 gives limits at the point of connection according to the short-circuit power.
Enter the fundamental current and the spectrum (each harmonic in % of the fundamental, with its angle). You can start from a typical spectrum. The angle only affects the waveform and the crest factor; the other results do not depend on it.
Each phase feeds switch-mode supplies with I₁ = 10 A and a spectrum of 3rd 80 %, 5th 60 %, 7th 40 %, 9th 20 %, 11th 10 %.
The neutral carries 24.7 A with 14.9 A per phase: had it been sized with half the cross-section, it would overheat.