Operation, autotransformers and other types
A transformer is a static electrical machine, with no moving parts, that changes the voltage and current of an AC system while keeping the frequency. It allows energy to be generated at one voltage, transmitted at a much higher one to reduce current and line losses, and then stepped down to values that are safe for the user.
Depending on the direction of conversion we speak of step-up or step-down transformers, although in general they are reversible as long as the voltage and power of each winding are respected. With no friction, their efficiency is very high: over 95 % in small units and above 99 % in large ones.
By core shape:
When an AC voltage is applied to the primary, a small current flows that creates an alternating flux in the core. That flux also links the secondary and induces an EMF in it, according to Faraday's law. With direct current the flux would be constant and nothing would be induced: the primary would act as a short circuit limited only by its resistance, and it would burn out.
The voltage induced in each winding is proportional to its number of turns:
with \(B_{max}\) the peak flux density in the core (T) and \(S\) its net iron cross-section (m²). In an ideal transformer, with no losses or leakage, the turns ratio applies:
If \(m > 1\) it is step-down, if \(m < 1\) step-up and if \(m = 1\) an isolation transformer. Power is always rated in volt-amperes (VA or kVA), because what heats the windings is the current, whatever the power factor of the load.
Core with a net cross-section of 10 cm² (\(S = 0.001\ \text{m}^2\)), with \(B_{max} = 1.2\ \text{T}\) at 50 Hz. Each turn gives \(4.44\cdot 50\cdot 1.2\cdot 0.001 = 0.266\ \text{V}\), that is, \(3.75\) turns per volt.
For a 230 V primary: \(230\cdot 3.75 \approx 863\) turns. For a 24 V secondary it is usual to add 5–10 % for the drop on load: \(24\cdot 3.75\cdot 1.07 \approx 96\) turns.
A real transformer departs from the ideal through two kinds of losses, measured with two tests:
The voltage needed in that test, as a percentage of rated, is the short-circuit (impedance) voltage \(u_{k}\). It is typically 4 to 6 % in distribution transformers. It tells how much the voltage drops on load and how much current would flow in a real short circuit: \(I_{sc} = I_n\cdot 100/u_{k}\). It is also one of the values that must match to connect transformers in parallel.
Maximum efficiency is reached at the load where copper losses equal iron losses. When a transformer is switched on at no load, an inrush current of 5 to 15 times rated can flow for a few cycles, which the protection must tolerate.
To connect several windings together or in parallel you need to know their corresponding terminals, the ones with the same polarity at every instant. This is explained in coupled coils.
They can be three single-phase transformers (large banks) or, more usually, a three-limb core with a primary and a secondary on each limb. Each side can be connected in star (Y, y), delta (D, d) or zigzag (z). The connection is designated by a capital letter for the high-voltage side, a lower-case one for the low-voltage side, n if the neutral is brought out, and a number, the clock (phase-shift) number, which gives the shift between both voltages in multiples of 30°.
| Vector group | Shift | Typical use |
|---|---|---|
| Dyn11 | 330° | Low-voltage distribution: the delta absorbs third harmonics and the neutral accepts unbalanced loads |
| Yyn0 | 0° | Distribution with little unbalanced load |
| Yzn11 | 330° | Small distribution units with heavily unbalanced load |
| Yd11 / Dd0 | 330° / 0° | Power stations, interconnection and industrial transformers |
According to IEC 60076, terminals are marked 1U, 1V, 1W on the high-voltage side and 2U, 2V, 2W on the low-voltage side, with N for the neutral.
An autotransformer has a single winding with an intermediate tap: the input voltage is applied across the whole winding and the output is taken between the tap and one end (step-down), or the other way round (step-up). Primary and secondary share the common part, and the voltage ratio is still the turns ratio.
The advantage lies in the currents: the common part carries not \(I_2\) but the difference \(I_2 - I_1\), and part of the power passes straight from input to output by conduction, without being transformed. The winding only has to be sized for the own (design) power, which is lower than the throughput power delivered to the load:
A 400 to 230 V autotransformer delivering 10 kVA: \(I_1 = 10\,000/400 = 25\ \text{A}\) and \(I_2 = 10\,000/230 = 43.5\ \text{A}\). Only \(43.5 - 25 = 18.5\ \text{A}\) flow through the common part.
Own power: \(10\cdot(1 - 230/400) = 4.25\ \text{kVA}\). A two-winding transformer for the same duty would need iron and copper for 10 kVA.
The closer the input and output voltages, the greater the saving. That is why the autotransformer is ideal for ratios close to 1.
| Type | Feature | Uses |
|---|---|---|
| Isolation | 1:1 ratio, primary and secondary galvanically separated | IT systems in operating theatres, repairing mains equipment, floating measurements |
| Safety | Reinforced insulation and extra-low voltage output (SELV, no more than 50 V AC) | Swimming pools, toys, lamps, control panels |
| Control | Single-phase 230 or 400 V to 24, 48 or 110 V, tolerant of current peaks | Contactor coils and control circuits in electrical panels |
| Current (CT) | Primary of few turns in series with the line; 5 A or 1 A secondary | Metering and protection at high currents |
| Voltage (VT) | Standard 100 or 110 V secondary | Metering and protection at medium and high voltage |
| Toroidal | Ring core, low stray field, high inrush current | Audio, lighting, medical and electronic equipment |
| High-frequency | Ferrite core and frequencies of tens or hundreds of kHz; since \(E\) grows with \(f\), far fewer turns and less core are needed | Switch-mode power supplies, chargers, inverters |
| Welding | High leakage flux: the voltage falls sharply as current rises, which stabilises the arc | Stick (MMA) arc welders |
| Pulse | Small, ferrite-cored, transmits pulses with isolation | Gate firing of thyristors and power transistors |
| Zigzag (earthing) | Creates an artificial neutral in networks without one | Neutral earthing in delta networks |
| Rectifier, furnace, traction | Special designs for very high currents or harmonic-rich loads | Electrolysis, arc furnaces, railways |
⚠ The secondary of a current transformer must never be left open with the line on load: all the primary current would go into magnetising the core and a very high voltage would appear, dangerous for people and for the transformer itself. Conversely, the secondary of a voltage transformer must never be short-circuited.
Low-voltage safety and isolation transformers are covered by the EN 61558 series of standards; instrument transformers by the IEC 61869 series.
When rewinding, keep the number of turns and the wire size of each winding; if the voltage changes, recalculate the turns from the core's turns per volt and the wire size from the new current (usual densities of 2 to 3.5 A/mm² in small dry-type transformers, depending on cooling). Insulating paper goes between layers and the assembly is impregnated with varnish. When restacking the laminations, alternate the joints to keep the air gap to a minimum.