Dual-voltage motors

6, 9 and 12 lead connections for two supply voltages

Two ways to get two voltages

A dual-voltage motor is designed to run on two different supplies without changing the winding: what changes is how its coils are connected in the terminal box. At both voltages each coil receives the same voltage and gives the same power; at the higher voltage the current is lower in the same proportion. There are two systems:

SystemVoltage ratioNameplate examplesLeads
Star-delta\(\sqrt{3}\)230/400 V, 400/690 V, 220/380 V6
Series-parallel (split winding)2230/460 V, 220/440 V, 208-230/460 V9 or 12

The first is the usual one in Europe and under IEC standards; the second, in NEMA motors in North America and in much of Latin America, where 220-230 V and 440-460 V supplies coexist.

6 terminals: star or delta

Each phase is a single circuit with two ends (U1-U2, V1-V2, W1-W2). At the lower voltage it is connected in delta and at the higher one in star. Link placement, the nameplate and star-delta starting are explained in the guide to the star-delta connection.

9 leads, wye-connected

741852963
Each phase has two halves: the outer one, with leads 1-4, 2-5 and 3-6, and the inner one, with leads 7, 8 and 9, joined internally to the star point.

NEMA numbering follows a spiral: 1, 2 and 3 are the starts of the outer halves; 4, 5 and 6, their ends; 7, 8 and 9, the starts of the inner halves. At the higher voltage the two halves of each phase are in series; at the lower voltage, in parallel, forming two stars (YY).

VoltageL1L2L3Join
Higher (series), e.g. 460 V1234-7, 5-8, 6-9
Lower (parallel), e.g. 230 V1-72-83-94-5-6

At the lower voltage, leads 4, 5 and 6 joined together form the point of the second star. This is also the connection used by part-winding starting: start on 1-2-3 and then connect 7-8-9.

9 leads, delta-connected

VoltageL1L2L3Join
Higher (series)1234-7, 5-8, 6-9
Lower (parallel)1-6-72-4-83-5-9—

At the higher voltage the connection is the same as for the wye motor, but at the lower one it is different, so you need to know which type it is. If the nameplate is missing, a multimeter tells them apart: in the wye motor, leads 7, 8 and 9 have continuity with each other (through the internal star point) and the rest come in pairs (1-4, 2-5, 3-6); in the delta motor there are three groups of three leads with continuity.

12 leads

With all twelve leads brought out, the motor can be connected in star or delta at either voltage. This allows, for example, star-delta starting at both 230 V and 460 V.

ConnectionL1L2L3Join
Delta, lower voltage (parallel)1-6-7-122-4-8-103-5-9-11—
Delta, higher voltage (series)1-122-103-114-7, 5-8, 6-9
Wye, lower voltage (parallel)1-72-83-94-5-6, 10-11-12
Wye, higher voltage (series)1234-7, 5-8, 6-9, 10-11-12

The tables in this guide show the usual connections according to NEMA MG 1. Some manufacturers number or group the leads differently: the diagram on the nameplate or inside the terminal box cover always takes precedence.

What happens if it is connected wrongly

After connecting a dual-voltage motor, it is good practice to start it at no load and measure the current in all three phases: they should be similar to each other and well below the rated current. If the lead markings have been lost, identifying the halves and their polarity requires a specific test; when in doubt, take it to a rewind shop.

Single-phase dual-voltage motors

115/230 V single-phase motors follow the same idea: the main winding is split into two halves connected in parallel at 115 V and in series at 230 V, and in many of them the auxiliary winding is connected in parallel with one of the halves, so it always works at 115 V. How the main and auxiliary windings work is explained in the single-phase motor fundamentals.