Two speeds in a 1:2 ratio with a single winding
It is a three-phase induction motor with a single winding that can run with two numbers of poles, one twice the other, and therefore at two speeds in a 1:2 ratio. It is named after Robert Dahlander, who patented the connection at the end of the 19th century. Each phase is split into two halves with a centre tap brought out to the terminal box; by changing how those halves are connected, the motor switches from one pole number to the other.
| Poles (low / high) | Synchronous speed at 50 Hz | At 60 Hz |
|---|---|---|
| 4 / 2 | 1500 / 3000 rpm | 1800 / 3600 rpm |
| 8 / 4 | 750 / 1500 rpm | 900 / 1800 rpm |
| 12 / 6 | 500 / 1000 rpm | 600 / 1200 rpm |
Actual speeds are slightly lower because of slip.
Each phase has as many coil groups as there are poles at high speed. At high speed the current flows through the groups in alternating directions: one creates a north pole, the next a south pole, and so on; it is a whole-coiled winding. At low speed the current is reversed in half of the groups, so that they all create poles of the same polarity; between every two groups a pole of opposite polarity then appears, where the flux closes (consequent poles). The number of poles doubles and the speed halves.
That half-phase reversal is exactly what the terminal box does when changing from one connection to the other, without touching the winding.
Depending on how the half-phases are connected at low speed, there are two types of Dahlander motor, which behave differently:
| Type | Low speed | High speed | Torque | Power ratio (indicative) | Applications |
|---|---|---|---|---|---|
| Δ / YY | Delta | Double star | Roughly constant | High speed gives 1.4 to 1.8 times the low-speed power | Machine tools, conveyors, hoisting |
| Y / YY | Star | Double star | Variable: much lower at low speed | Low speed gives a quarter to a sixth of the high-speed power | Fans and centrifugal pumps |
The Y/YY type suits quadratic-torque loads: a fan at half speed needs only a quarter of the torque and an eighth of the power. There is also the YY/Δ connection, with constant power, which is uncommon. From the outside all three types are handled in the same way: the difference lies in the internal connections, and the nameplate shows it (for example "Δ/YY" or "Y/YY") together with the power and current for each speed.
| Speed | Supply L1-L2-L3 to | Links | Free terminals |
|---|---|---|---|
| Low | 1U - 1V - 1W | None | 2U - 2V - 2W (insulated) |
| High | 2U - 2V - 2W | 1U + 1V + 1W joined | None |
With contactors, switching needs three of them:
KM1 must be interlocked with KM2 and KM3, electrically and mechanically: if KM3 closed together with KM1, it would short-circuit the supply. As each speed has its own rated current, two overload relays are used, one at the output of KM1 and another at the output of KM2, each set to the nameplate current of its speed.
It is a normal three-phase winding, almost always double-layer, with two particular features. First, the number of groups: each phase has as many groups as there are poles at high speed, divided into two equal halves with the centre tap. Second, the coil pitch: a full pitch for the high speed would be twice the pole pitch of the low speed, so an intermediate pitch is chosen that works acceptably at both. The winding factor is not optimal at either speed, which is why a Dahlander motor performs slightly worse than a single-speed motor of the same size.
When rewinding, the pitch, the number of groups, the order of the halves and the internal connection (Δ or Y at low speed) must be kept, and the six leads must be clearly marked. Before assembly it is advisable to check the resistance of each half-phase and run a no-load test at both speeds.