Starting motors that have two parallel circuits per phase
Some motors have each phase made up of two identical circuits connected in parallel: two stars in parallel (YY) or two deltas (ΔΔ). Part-winding starting takes advantage of that split: the motor starts by energising only one of the two halves and, one or two seconds later, the other half is connected in parallel. With half the winding in service the impedance is higher and the starting current is reduced.
It is a very common method in North America, especially in refrigeration and air-conditioning compressors, chillers and pumps, where 230/460 V dual-voltage motors abound and, at the lower voltage, have precisely their two halves in parallel.
As the motor is never disconnected during the change, this is a closed-transition start: it does not have the current peak that appears when changing from star to delta.
One might expect half the winding to draw half the current, but the two halves share the slots and are magnetically coupled, so the reduction is smaller. Indicative values:
With only one half the field is less uniform: the torque curve may have a dip that prevents the motor from reaching rated speed, and the motor is noisier and heats up faster. That is why the second step is connected on time, whatever speed the motor has reached; this start is not meant for the motor to fully accelerate on half the winding.
A compressor with a 230/460 V motor on a 230 V supply, rated 62 A, with a direct-on-line starting current of 6.5 times rated (about 400 A). With part winding the first step would draw around \(0.65\cdot 400 \approx 260\ \text{A}\), and the starting torque would be roughly half the DOL value: enough for a compressor that starts with equalised pressures.
The guide to dual-voltage motors explains how the leads are numbered and how the two halves are connected.
Each half of the winding carries half the rated current. Both contactors are chosen for somewhat more than half the motor current, and it is usual to fit one overload relay per half, each set to half the rated current. That way, if KM2 fails to close, the motor left running on half the winding trips on overload instead of burning out. Short-circuit protection (fuses or circuit breaker) protects the whole circuit.
| Part winding | Star-delta | |
|---|---|---|
| Contactors | 2 | 3 |
| Transition | Closed, no peak | Open, peak at changeover |
| Starting current | ≈ 60–70 % of DOL | ≈ 33 % of DOL |
| Starting torque | ≈ 45–50 % of DOL | ≈ 33 % of DOL |
| Duration of the first step | 1–2 s, on time | Until close to rated speed |
| Motor | Two parallel circuits (9 or 12 leads) | 6 terminals, Δ at supply voltage |
In short: part winding reduces the current less, but gives more torque and a simpler, smoother transition. It suits cases where the utility or a generator set limits the starting peak and the load is not heavy.
The two halves must be identical: same turns, same wire and same pitch. If one has more turns than the other, a current circulates between them once they are in parallel, heating the motor even at no load. You must also keep the same coil groups in each half as in the original winding, because that grouping decides whether one half alone produces an acceptable field during the start. Before cutting the end windings, note which lead each group goes to.
In the usual type (1/2) the winding has two circuits and the motor starts on one. Some motors have three circuits in parallel and start on two (2/3): the starting current is reduced less than with 1/2, but the torque is higher and the field more uniform.
Usually about 1 second, and hardly ever more than 2. Do not lengthen it to let the motor pick up more speed: with half the winding it heats up quickly and its torque may not be enough to accelerate fully.
The motor keeps running on half the winding, noisily, with little torque and close to twice the current in that half. If the overload relays are set to half the rated current, the one on the first half trips after a short time.
There is no need: with a soft starter or a variable frequency drive the motor is connected from the start with both halves in parallel (1-7, 2-8, 3-9 and 4-5-6 joined) and the device limits the current.
No, because its halves are not accessible from the terminal box. For such a motor the contactor-based alternative is the star-delta start, if it runs in delta at the supply voltage.