How to Connect a Three-Phase Motor to a Single-Phase Supply

Introduction

As we have seen in other sections, the three-phase induction motor is a very simple, effective and inexpensive machine. It is no coincidence that electrical energy is generated and distributed as three-phase power, at least as far as large consumers. Small consumers, however, receive electricity over two wires, either single-phase or two-phase (in reality two phases of a three-phase system; true two-phase power is something else and very uncommon).

Sometimes we need to power a three-phase motor and only a single-phase supply is available. The elegant solution is to fit a variable frequency drive (VFD) with a 230 V single-phase input and connect the motor (if it is rated 230/400 V) in delta to the drive output (three-phase at 230 V). This solution is relatively expensive, but the motor delivers its full performance. The other option is to feed it directly from the single-phase supply: it is cheaper and needs no configuration, but we lose mechanical performance. If that is not critical, the motor can be run with just one capacitor.

Three-phase motors work as described in Fundamentals of induction motors: whether connected in star or delta, each phase carries a current shifted 120° from the others, which ensures smooth, powerful rotation and a very good starting torque.

When connecting a three-phase motor to a single-phase supply, the first thing to check is the voltage the motor is rated for, usually shown as xxx/xxx V on the nameplate, and the supply voltage. From these we know whether the motor must be connected in delta or in star.

Three-phase to single-phase connection options

Motor voltage
Supply voltage 130/230V 230/400V 400/690V
130 Delta Not possible Not possible
230 Star Delta Not possible
400 Not possible Star Delta

As you can see, the options are limited, and this type of connection is not recommended for motors above 5 kW. The required capacitor is found with the formula below. In short, the capacitive reactance of the capacitor must be equal or close to the inductive reactance of one of the phases (be careful not to confuse it with the resistance or the impedance). The aim is to achieve parallel resonance, although there is some tolerance either way. It is advisable to round the capacitor value up: a capacitor that is too small will not even let the motor start, while one that is too large causes excess current in one of the windings, which can overheat or even burn out the motor. If more starting torque is needed, a second capacitor must be added, but it has to be disconnected once the motor reaches its running speed.

For delta connection $$ C = \frac{1}{\omega \cdot X_L} $$ $$ C\,\text{in}\,\text{F} $$ $$ X_L\,\text{in}\,\Omega $$
For star connection $$ C = \frac{1}{3\cdot\omega \cdot X_L} $$ $$ C\,\text{in}\,\text{F} $$ $$ X_L\,\text{in}\,\Omega $$

We usually do not know the inductive reactance of each winding, so another way to find the required capacitor is from the motor power:

For delta connection $$ C = 70 \cdot P $$ $$ C\,\text{in}\,\mu\text{F} $$ $$ P\,\text{in}\,kW $$
For star connection $$ C = 23.33 \cdot P $$ $$ C\,\text{in}\,\mu\text{F} $$ $$ P\,\text{in}\,kW $$

Take the case of a 230/400 V motor that has to be connected to a 230 V single-phase supply: the terminal board is therefore connected in delta. Connect the two supply wires to any two of the three terminals (U, V, W), and the capacitor between either supply wire and the remaining terminal. To reverse the direction of rotation, simply move the capacitor wire from U to V. Swapping the supply wires does not change the direction of rotation of the rotor.

This produces a set of phasors which, although not as perfect as the one obtained from a three-phase supply, is good enough for the motor to turn and drive most machines. Note that only the motor phase connected between L and N draws its rated current, and it stays constant whatever capacitor value is used. If the capacitor is not the ideal one for the motor, the other two phasors (currents) will change in magnitude and angle.

Phase U - X

Phase V - Y

Phase W - Z

N

Approximate diagram for the delta connection; in star the phasor magnitudes and angles change slightly.

   Phase voltage: V