Alternators and synchronous motors: parts, operation and windings
A synchronous machine is an AC machine whose rotor turns at exactly the same speed as the rotating field of the stator, the synchronous speed. Unlike an induction motor there is no slip: if the supply frequency is constant, so is the speed, at any load.
with \(n_s\) in rpm, \(f\) the frequency in Hz and \(p\) the number of pole pairs. Almost all the world's electricity is produced by synchronous machines working as alternators: in thermal, nuclear and hydro plants, in generator sets and in many wind turbines. As a motor it is used in large constant-speed drives (compressors, mills, high-power pumps), as a reactive-power compensator and, in its permanent-magnet version, in servomotors and electric vehicles.
| Poles | 2 | 4 | 6 | 8 | 12 | 24 | 48 |
|---|---|---|---|---|---|---|---|
| rpm at 50 Hz | 3000 | 1500 | 1000 | 750 | 500 | 250 | 125 |
| rpm at 60 Hz | 3600 | 1800 | 1200 | 900 | 600 | 300 | 150 |
Steam and gas turbines are fast and drive 2- or 4-pole alternators; hydraulic turbines and slow diesel engines need alternators with many poles.
It is practically the same as that of a three-phase induction motor: a stack of slotted electrical steel with a distributed three-phase winding. The voltage is induced in it (alternator) or the supply energy enters through it (motor). That is why the stator winding rules are the same as those explained in the induction motor fundamentals.
The rotor creates the magnetic field. There are two constructions:
The rotor winding is fed with direct current. In classic machines it arrives through two slip rings with brushes, from an exciter dynamo or a rectifier. In modern alternators the usual system is brushless excitation: a small exciter alternator on the same shaft generates AC, rotating diodes rectify it and feed it straight to the main rotor. An automatic voltage regulator (AVR) adjusts the field current.
Many machines have short-circuited bars in the pole shoes, like a squirrel cage. In a motor they are used to start it as an induction motor, and in both cases they damp rotor oscillations when the load changes suddenly.
The RMS EMF induced in each stator phase is:
where \(Z\) is the number of slots, \(m\) the number of phases, \(q\) the slots per pole per phase, \(\alpha\) the electrical angle between slots, \(y\) the coil pitch and \(\tau_p = Z/2p\) the pole pitch, both in slots.
A 36-slot, 4-pole (\(p = 2\)) three-phase stator with a short pitch of 8 slots. Then \(q = 36/(4\cdot 3) = 3\), \(\alpha = 2\cdot 360^\circ/36 = 20^\circ\) and \(\tau_p = 9\).
\(k_d = \sin 30^\circ/(3\cdot\sin 10^\circ) = 0.960\); \(k_p = \sin(8/9\cdot 90^\circ) = \sin 80^\circ = 0.985\); \(k_w = 0.945\).
Short pitching is not a whim: with \(y/\tau_p \approx 5/6\) the 5th and 7th harmonics are greatly reduced and the voltage is closer to a pure sine wave, at the cost of a little voltage.
When an alternator supplies its loads on its own, as in a generator set, the speed of the prime mover sets the frequency and the field current sets the voltage. As the load increases, the voltage tends to drop (especially with inductive loads) and the AVR raises the excitation to compensate. The engine governor, in turn, holds the frequency.
Connected to a grid much larger than itself, the voltage and frequency are imposed by the grid. The controls then change roles: the turbine torque controls the active power delivered, and the excitation controls the reactive power. Over-excited, it supplies reactive power to the grid (it behaves like a capacitor); under-excited, it absorbs it (like an inductor).
Before closing the breaker that connects it to the grid it must be synchronised. These must match:
This is checked with a synchroscope, a synchronism-check relay or, in simple installations, with lamps between corresponding phases: the breaker is closed when the lamps are dark. Connecting out of phase causes a torque and current shock that can damage the shaft, the coupling and the windings.
A synchronous motor connected directly to the supply does not start by itself: the stator field turns at synchronous speed from the first instant, the rotor cannot follow it and the average torque is zero. It is started as an induction motor thanks to the damper winding, with the field winding closed through a resistor, and when it nears synchronous speed the excitation is applied and the rotor "pulls into step". It can also be started with a pony motor or, most commonly today, with a frequency inverter.
On load, the rotor lags the stator field by a load angle \(\delta\). In a cylindrical-rotor machine, neglecting resistance:
with \(U\) and \(E\) phase voltages and \(X_s\) the synchronous reactance. Maximum power occurs at \(\delta = 90^\circ\); if the load demands more, the rotor loses synchronism and the machine pulls out of step. That is why an over-excited motor, with higher \(E\), copes better with torque peaks.
At constant power, varying the excitation changes the stator current and its phase angle. Plotting current against excitation gives a V-shaped curve whose minimum corresponds to \(\cos\varphi = 1\). With low excitation the motor absorbs inductive reactive power; when over-excited it supplies reactive power to the grid and improves the power factor of the whole installation. A synchronous motor running unloaded just for that purpose is called a synchronous condenser.
It is designed with the same rules as the stator of a three-phase induction motor: slots per pole per phase, single or double layer, concentric or lap coils and short pitching. Two particular points:
When rewinding a pole, keep the number of turns, the wire size and the winding direction. Then measure the voltage drop across each pole with the field fed from DC: it must be the same on all of them, and a compass must show the N–S alternation.
According to IEC 60034-8, the three-phase stator has the same terminals as an induction motor and the field has its own letters:
| Winding | Terminals |
|---|---|
| Three-phase stator | U1 – U2, V1 – V2, W1 – W2 (N for neutral) |
| Field (rotor) | F1 – F2 |