Size your capacitor bank automatically
Calculate the power and capacitance of the capacitor bank needed to improve the power factor (cos φ) of an installation, or check which cos φ you will get with a given bank.
Motors, transformers, ballasts and other inductive equipment need to create magnetic fields in order to work. To do so they draw, in addition to the active energy that is converted into useful work, reactive energy that flows back and forth between the supply and the load without doing any work. This reactive energy overloads lines and transformers, increases losses and voltage drop, and the utility usually charges for it when it exceeds certain limits.
The power factor (cos φ) shows what part of the apparent power is active. A cos φ of 1 means there is no reactive power; the lower it is, the more reactive power flows through the installation.
A capacitor generates reactive energy of the opposite sign to that of inductive loads. By installing a capacitor bank close to the loads, the reactive power required by the motors is supplied by the capacitors instead of the grid, so less current flows through the service connection and the cos φ seen by the utility improves.
Multiply the active power (kW) by the k factor to get the kvar required.
| Current cos φ | → 0.95 | → 0.98 | → 1.00 |
|---|---|---|---|
| 0.60 | 1.005 | 1.130 | 1.333 |
| 0.70 | 0.692 | 0.817 | 1.020 |
| 0.75 | 0.553 | 0.679 | 0.882 |
| 0.80 | 0.421 | 0.547 | 0.750 |
| 0.85 | 0.291 | 0.417 | 0.620 |
| 0.90 | 0.156 | 0.281 | 0.484 |
A three-phase industrial unit at 400 V and 50 Hz draws 50 kW at cos φ = 0.75, and the target is 0.95. Qc = 50 · (0.882 − 0.329) ≈ 27.7 kvar. With the capacitors connected in delta, each one needs C = 27,700 / (3 · 314.16 · 400²) ≈ 184 µF. The line current drops from about 96 A to about 76 A, freeing up capacity in cables and transformer.
Avoid overcorrecting: with a leading (capacitive) cos φ, overvoltages may appear and there may also be penalties. If the load varies during the day, an automatic stepped bank is better than a fixed one. In installations with variable frequency drives or other non-linear loads, consider detuned capacitors (with harmonic blocking reactors) to avoid resonance.
Related: series and parallel RLC circuit calculator.
This tool provides an approximate calculation. For real installations, check the rated voltage of the capacitors, the protection, the presence of harmonics and the applicable regulations and tariff.