Calculate the voltage drop of an electrical line, or the minimum cable cross-section needed to stay within the allowed drop, for DC, single-phase or three-phase circuits.
Every conductor has electrical resistance. When current flows through it, part of the voltage is lost along the cable, so the voltage reaching the load is lower than at the source. That difference is the voltage drop. If it is too high, motors struggle to start and overheat, lighting loses output and electronic equipment may malfunction.
The drop depends on the current flowing, the length of the line, the conductor cross-section and the material (copper or aluminium). The longer the line or the higher the current, the greater the drop; the larger the cross-section, the smaller the drop. So, once the maximum allowed drop is known, the minimum cross-section required can be worked out.
The calculator uses the usual low-voltage formulas, which only take the cable resistance into account:
The percentage drop is measured against the supply voltage (line-to-line in three-phase):
Solving for the cross-section, the minimum size that keeps the drop below ΔV is given below; then pick the next standard size up:
L is the line length in metres (one way), I the current in amperes, S the cross-section in mm², V the voltage (line-to-line in three-phase) and γ the conductivity of the material in m/(Ω·mm²).
| Material | 20 °C | 70 °C (PVC) | 90 °C (XLPE / EPR) |
|---|---|---|---|
| Copper | 56 | 48 | 44 |
| Aluminium | 35 | 30 | 28 |
A 3500 W heater at 230 V (cos φ = 1), 30 m away, on 2.5 mm² copper cable at 70 °C (γ = 48). The current is I = 3500 / 230 = 15.2 A and the drop is ΔV = 2 · 30 · 15.2 / (48 · 2.5) = 7.6 V, or 3.3 %. It meets a 5 % limit but not a 3 % one: for 3 % (6.9 V) you would need S = 2 · 30 · 15.2 / (48 · 6.9) = 2.76 mm², so 4 mm², with a 4.8 V drop (2.1 %).
A motor drawing 15 kW at 400 V with cos φ = 0.85, 80 m away, copper at 70 °C, with 5 % allowed (20 V). I = 15 000 / (√3 · 400 · 0.85) = 25.5 A. S = √3 · 80 · 25.5 · 0.85 / (48 · 20) = 3.1 mm², so you choose 4 mm², with a 15.6 V drop (3.9 %). In aluminium (γ = 30) it would come out at 5.0 mm², so 6 mm².
Each country sets its own limit. These are the most common reference values:
| Standard or country | Lighting | Other uses | Notes |
|---|---|---|---|
| IEC 60364-5-52 (Annex G) | 3 % | 5 % | Supply from the public low-voltage network. With a private transformer, 6 % and 8 %. |
| United Kingdom: BS 7671 (Appendix 4) | 3 % | 5 % | Same values as IEC; 6 % and 8 % with a private supply. |
| Australia and New Zealand: AS/NZS 3000 | 5 % | 5 % | From the point of supply to any point of the installation. |
| United States: NEC (informational note) | 3 % | 3 % | 3 % on the branch circuit and 5 % in total with the feeder. It is a recommendation, not a requirement. |
| Spain: REBT (ITC-BT-19) | 3 % | 5 % | From the origin of the indoor installation. Individual supply line: 1.5 % (1 % with centralised meters). |
Reference values summarised by us; check the current edition of the standard and the type of installation before applying them.
Aluminium conducts worse than copper: at the same temperature its conductivity is about 1.6 times lower (30 versus 48 at 70 °C). For the same drop you therefore need a cross-section 1.6 times larger, usually the next standard size or two sizes up. In return it is much lighter and cheaper, which is why it is used on long, large-section runs. In practice, aluminium is rarely installed below 16 mm².
One-way only: the distance from the source to the load. In single-phase and DC the 2 in the formula already counts the return conductor; in three-phase the √3 accounts for the three phases.
In a balanced three-phase line no current returns through the neutral, and the drop is measured line-to-line, which is √3 times the drop in each conductor.
No. For small sizes it is negligible compared with the resistance. Above about 50 mm², or with a low cos φ, the real drop is somewhat higher than calculated.
No. The cable must also carry the current without overheating (current-carrying capacity for the installation method) and withstand the short circuit until the protection trips. Choose the largest of the sizes you get.
Yes, with the “DC” system. Bear in mind that at 12 V, 3 % is only 0.36 V, so you need much larger cables than at 230 V for the same power.
No. It is meant for low voltage (up to 1000 V AC and 1500 V DC). At medium and high voltage the cable reactance and capacitance matter, and other methods are used.
This tool provides an approximate calculation. For real projects, also check the cable's current-carrying capacity, overload and short-circuit protection, and the regulations in force.