Luminaire classification

By flux distribution, beam angle, outdoor lighting and protection

Luminaires are classified in several ways depending on what matters: how they split light between ceiling and floor, how concentrated their beam is, how much light they send to the sky outdoors, or what protection they have against electric shock, dust and water. The classifier shows the first two for a luminaire you can adjust.

Classifier

Luminaire

1. By luminous flux distribution (CIE)

This is the classic CIE classification. It looks at what part of the luminaire flux goes to the lower hemisphere (towards the floor) and what part to the upper one (towards the ceiling):

TypeDownwardsUpwardsFeatures and uses
Direct90–100 %0–10 %Maximum use of light and a dark ceiling. Downlights, recessed panels, high-bays, floodlights.
Semi-direct60–90 %10–40 %Lights the ceiling a little and reduces the contrast with the luminaire. Suspended luminaires with an upper opening.
General diffuse40–60 %40–60 %Light in all directions, like an opal globe. If it emits little horizontally it is called direct-indirect.
Semi-indirect10–40 %60–90 %Soft light and few shadows. Floor lamps and design pendants.
Indirect0–10 %90–100 %All the light arrives reflected from the ceiling: no glare or shadows, but it needs light ceilings and more power.

The more indirect the lighting, the more it depends on the colour of the ceiling: with a white ceiling (\(\rho\) = 0.8) it is used well; with a dark one, much of the light is lost (see reflectance factors). In return, indirect light is more comfortable and reduces reflections on screens.

2. By beam angle

The beam angle is the full angle within which the intensity is at least half the maximum. The field angle is the same angle measured at 10 %. Outside it the light is negligible. On datasheets it can be seen in the polar curve.

NameBeam angle (50 %)Typical uses
Narrow spot< 15°Accenting small objects, very high ceilings, long-distance projection
Spot15–30°Shop windows, paintings, accent spotlights, high-bays in very tall halls
Flood (medium)30–60°Downlights, lighting counters and zones
Wide flood60–90°General lighting with medium or high ceilings
Very wide> 90°Panels, battens, ceiling lights: general lighting with low ceilings

The ranges vary somewhat between manufacturers: there is no single standard for these names.

As a rule, the higher the ceiling, the narrower the beam must be so that light reaches the working plane and is not lost on the walls; and the lower the ceiling, the wider it must be so that the lighting is uniform without installing many luminaires.

NEMA floodlight types

For floodlights the NEMA (United States) classification is widely used. It is based on the field angle, at 10 % of the maximum intensity:

NEMA typeField angleDescription
110–18°Very narrow
218–29°Narrow
329–46°Medium narrow
446–70°Medium
570–100°Medium wide
6100–130°Wide
7> 130°Very wide

A floodlight can have a different spread horizontally and vertically; then both types are given, for example "NEMA 6 × 4". Symmetrical floodlights have a round or square beam; asymmetric ones send light more forwards than upwards and are used for façades, signs and courts, because they let the floodlight be mounted horizontally and reduce glare.

3. Outdoor lighting: light to the sky

Outdoors, what matters most is how much light escapes above the horizon, because that is what produces sky glow or light pollution.

A modern street light with flat glass mounted horizontally has practically zero upward light. Tilting it to "reach further" increases it and usually worsens glare.

4. By protection

Protection against electric shock

ClassProtectionRequirement
Class IBasic insulation and metal parts connected to the protective conductorEarth connection mandatory
Class IIDouble or reinforced insulation (symbol of two squares)Not earthed
Class IIISupply at safety extra-low voltage (SELV, up to 50 V AC)Isolated safety source

IP and IK protection ratings

The IP code (EN 60529) indicates protection against solids (first digit, 0 to 6) and against water (second, 0 to 8). Common values: IP20 in dry interiors, IP44 in bathrooms outside the shower zone, IP65 outdoors and in areas with water jets, IP66 or higher in the food industry and IP67/IP68 for in-ground or submersible luminaires. The IK code (EN 62262) measures impact resistance, from IK00 to IK10; in sports halls or areas at risk of vandalism IK08 or higher luminaires are used.

5. By mounting

Recessed (in suspended ceilings), surface-mounted, suspended, track, wall lights, floor lamps, table lamps, floodlights, bollards, columns and brackets, in-ground and weatherproof. The mounting determines the possible distribution: a recessed luminaire can only be direct, while a suspended one can be of any type.

Related: photometric diagrams, point-by-point method, lux, lumen and candela converter and colour temperature.