Forces between conductors

The magnetic field of a current, the force between two conductors and short-circuit forces on a busbar

Every current-carrying conductor creates a magnetic field in rings around it, and any other current-carrying conductor inside that field feels a force. With normal currents those forces are small. In a short circuit, with tens of kiloamperes, they can bend busbars, break insulators and tear cables out of their cleats.

Field of a conductor and force between two

The field of a long straight conductor falls with distance, and the force per metre between two parallel conductors is proportional to the product of their currents:

\[ B = \frac{\mu_0\, I}{2\pi\, r} \]

\[ \frac{F}{l} = \frac{\mu_0\, I_1\, I_2}{2\pi\, d} = 2\cdot 10^{-7}\,\frac{I_1\, I_2}{d}\ \text{N/m} \]

Simulator

Show

· current coming out, × going in. The yellow lines are field lines and the orange arrows the force on each conductor. Drag the conductors; tap an empty spot to measure B. In the three-phase case, the horizontal force on L2 (orange) and L1 (violet) is plotted below.

Things to try

Short-circuit forces on a busbar

In a three-phase short circuit, the centre phase suffers most. According to IEC 60865, the maximum force on it between two supports a distance l apart is:

\[ F_{m3} = \frac{\mu_0}{2\pi}\,\frac{\sqrt{3}}{2}\, i_p^2\,\frac{l}{a_m} \qquad i_p = \kappa\,\sqrt{2}\,I_k'' \]

ip is the peak short-circuit current: the symmetrical current \( I_k'' \) plus the DC component of the first half-cycle. The factor κ ranges from 1.02 in very resistive networks to 2 in very inductive ones; near a large transformer it is usually between 1.7 and 1.9. am is the effective distance between phases, which for single bars is almost the centre-to-centre distance.

Equivalent static force, ignoring the busbar's own vibration and how the load is shared between supports. To size bars and insulators, follow IEC 60865 or the switchboard maker's test data.

Example

A switchboard next to a 1000 kVA transformer may see about 25 kA of short-circuit current. With κ = 1.8, the peak is 64 kA. With phases 10 cm apart and supports every 50 cm, the force on the centre phase is about 3500 N: more than 350 kg pushing on the middle of a half-metre span, for a few tenths of a second.