What the device's figures say and what happens inside when it opens
Opening a circuit under load is relatively easy. Opening it with thousands of amperes is another matter: as the contacts separate an arc appears that keeps conducting, and it has to be extinguished without destroying the device. Breaking capacity is the largest current at which a device guarantees to achieve this.
| Symbol | What it means | Where it appears |
|---|---|---|
| Icn | Rated breaking capacity of a modular device. After the test, it is not required to remain in perfect condition. | EN 60898, in amperes: 6000, 10000... |
| Icu | Ultimate breaking capacity: it breaks, but may be left unusable. | IEC 60947-2, in kA and according to voltage. |
| Ics | Service breaking capacity: it breaks several times and keeps working. | As % of Icu in IEC 60947-2: 25, 50, 75 or 100 %. |
| Icm | Making capacity: the peak it withstands when closing onto a fault. | kA peak: n × Icu. |
| Icw | Short-time withstand current, for a given time without tripping. | Category B breakers, for selectivity. |
In modular devices, EN 60898 relates Ics to Icn: 100 % up to 6 kA, 75 % between 6 and 10 kA with a minimum of 6 kA, and 50 % above that with a minimum of 7.5 kA. In industrial devices, IEC 60947-2 sets the minimum Icm according to Icu:
| Icu (kA) | cos φ | n = Icm/Icu |
|---|---|---|
| 4.5 – 6 | 0.7 | 1.5 |
| 6 – 10 | 0.5 | 1.7 |
| 10 – 20 | 0.3 | 2.0 |
| 20 – 50 | 0.25 | 2.1 |
| > 50 | 0.2 | 2.2 |
Values quoted from EN 60898 and IEC 60947-2, without checking against the official text. The device's data sheet prevails, at the service voltage: breaking capacity falls as voltage rises.
When the contacts separate, the air ionises and the current continues through a very hot plasma. But in AC, the current reaches zero every half cycle, and at that moment the arc stops receiving energy. The device's job is to cool and lengthen it so that, after the zero, the gap between contacts withstands the voltage that reappears, called the transient recovery voltage. If it does not, the arc re-ignites and has to wait for the next zero.
That is why devices have chambers with metal plates that split the arc into many arcs in series, a magnetic field that pushes it towards them and, at medium and high voltage, media that recover insulation very quickly, such as vacuum or SF₆. A more inductive circuit is harder: at its current zero, the source voltage is almost at maximum.
In DC there is no zero to help. The arc itself has to create it: only if the arc voltage Ua exceeds the source voltage does the current start to fall. Meanwhile the arc receives the energy of the inductance and what the source keeps supplying. Try lowering the arc voltage below U:
In the simulator the current starts from U/R and the arc voltage is constant, a useful simplification. This gives the practical rules for DC:
Fuses and many modern circuit breakers act so fast that they open before the first peak arrives: they are current limiters. The peak they let through is much lower than the prospective one, and so is the energy I²t, which is what heats the cable:
This also allows cascading or back-up protection: a strongly limiting upstream device helps a downstream one with lower breaking capacity. It is valid only with the combinations published by the manufacturer, and selectivity is usually lost in exchange.
See also: Short-circuit current calculator, Short circuit in DC and AC, Protection curves and Protective devices.