Short-circuit transient

How the current builds up in DC and AC, and which instant t₀ gives each maximum

1. Simulator

Source and fault
Hz
ms
V
mΩ
mΩ

Current after the fault

Maxima according to t₀

Horizontal axis: voltage angle when the fault occurs, over one period. Move the slider and the red line marks the chosen instant. Zero current is assumed before the fault.

How to use it

Choose the source, enter its data and move the instant t₀. The opening time tk is when the protection cuts off: it gives the current to be interrupted and the energy ∫i²dt. To obtain R and X for a real installation, use the short-circuit current calculator.

The three instants that matter in AC

\[ i(t) = I_m\left[\sin(\omega t - \varphi) - \sin(\omega t_0 - \varphi)\,e^{-(t-t_0)/\tau}\right],\quad t \ge t_0 \]

The current cannot jump: the inductance forces it to start at zero. That is why a DC component appears, dying away with τ = X/(ωR), and its size depends only on t₀.

Next to an alternator

\[ I(t) = (I_k''-I_k')\,e^{-t/T_d''} + (I_k'-I_k)\,e^{-t/T_d'} + I_k \]

Close to an alternator, the AC component itself decays because the rotor flux is not maintained: from the subtransient current Ik'' to the transient Ik' and the steady-state Ik, which may be lower than the protection's rating. The default values are only an example: use those from the alternator's manufacturer.

In direct current

\[ i(t) = I_k + (I_0 - I_k)\,e^{-t/\tau} \qquad I_k = \frac{U}{R} \qquad \tau = \frac{L}{R} \]

In DC there is no worst instant: the voltage is always the same, so t₀ changes nothing. The current rises without exceeding Ik and never passes through zero. With a short τ it very quickly reaches a value the device has to extinguish with no help from a natural zero.

Limits of the model

R and X are assumed constant, with no saturation or conductor heating and no arc at the fault. It models a single phase, with zero prior current in AC and no motor contribution. It is for understanding and estimating; a formal study follows IEC 60909, or IEC 61660 for DC.