What happens when an RL or RC circuit is connected to the mains, depending on the switching instant

1. Switch-on simulator

Circuit and switching
V
Hz
Ω
mH

It is assumed that before closing there is no current in the inductor and no charge on the capacitor. Move the switching angle and watch how the transient component (green) changes while the steady-state one (blue) always stays the same.

2. Practice problems

Problem type

Steady state and transient

When a linear circuit is connected to a sinusoidal voltage, the response is the sum of two parts. The steady-state component is the one we calculate with phasors: a sinusoid of the source frequency, with amplitude Vm/Z and phase shift φ. The transient component is an exponential that dies away with the circuit time constant, just as in DC. Its size is not fixed: it is exactly what is needed for the inductor current, or the capacitor voltage, to start at the value it had before switching. That is why it depends on the switching instant.

Switching on an RL circuit: asymmetry

\[ v = V_m \sin(\omega t + \alpha) \qquad \varphi = \arctan\frac{\omega L}{R} \qquad \tau = \frac{L}{R} \]
\[ i(t) = I_m\left[\sin(\omega t + \alpha - \varphi) - \sin(\alpha - \varphi)\,e^{-t/\tau}\right] \]

If the switch closes exactly when α = φ, the transient component is zero and the current starts straight in steady state. If it closes at α = φ − 90°, the initial DC component equals Im and the current is shifted to one side of the axis: an asymmetrical current, whose first peak approaches twice the steady-state peak when the resistance is small compared with the reactance. In highly inductive circuits (φ near 90°) the worst case is closing as the voltage crosses zero.

This is what happens in a short circuit on the network: the switching device must withstand the asymmetrical peak, not just the rms value. IEC 60909 estimates it with the factor κ, which depends on the R/X ratio of the network:

\[ i_p = \kappa\,\sqrt{2}\,I_k'' \qquad \kappa \approx 1.02 + 0.98\,e^{-3R/X} \]

κ ranges from 1.02 in very resistive networks to almost 2 in very inductive ones, such as those close to power transformers. The making capacity of circuit breakers is specified precisely as a peak value. The κ formula is quoted from IEC 60909; a formal calculation must follow the standard and its correction factors.

Something similar happens when a transformer is energised at no load, although there the inrush current is much larger because of core saturation, which this linear model does not include.

Switching on a capacitor

A discharged capacitor behaves at the first instant like a short circuit, so the initial current is v(0)/R: if it is connected as the voltage passes its peak, only the resistance (and in reality the inductance) of the circuit limits the surge. This is the reason for pre-insertion resistors or reactors and for special contactors for power factor correction capacitor banks. Connecting at the voltage zero crossing, or with the capacitor already charged to the mains voltage at that instant, avoids the surge.

With the network inductance in series, switching a capacitor forms an RLC circuit: a high-frequency oscillation also appears, which can cause overvoltages of up to twice the peak voltage.

See also: DC transients, Phasor problems, RLC circuit and Power factor correction.