Single-phase and three-phase, with sources of several frequencies and phases
Draw the circuit, press Solve and you get the voltages, currents and powers of each element, with their phasors and waveforms. For pure DC there is the DC circuit analyzer, which also shows the mesh formulation.
How to draw. Press an element to add it and drag it. Press one terminal and then another to join them with a wire: on the way, a click on empty space makes a corner and a click on a wire opens a junction. With an element selected, change its data in the panel. The R key rotates and Del deletes; there are buttons too.
Examples:
You have changed the circuit: press Solve to update the results.
Results
Elements
Total RMS values. Press a row to see that element in detail.
Phasors
Solid: voltages. Dashed: currents. Each group has its own scale.
Waveforms
With all frequencies added. Voltages above, currents below.
Node voltages
Relative to ground.
Step-by-step solution
At each frequency, modified nodal analysis with phasors: first with symbols and then with their values, as in the DC analyzer. Three-phase elements appear split into their phases.
Several frequencies at once
Each source accepts a list of components, each with its value, frequency and phase. At 0 Hz, that component is DC and its value carries the sign. The circuit is solved by superposition: once per frequency, with the other components at zero, that is, voltage ones shorted and current ones open. An inductor is a short circuit at DC and a capacitor, an open circuit.
The total is obtained like this: the RMS value is the square root of the sum of the squares at each frequency, and P is the sum of the P at each frequency. Currents and voltages of different frequencies give no average power.
Power with several frequencies
Q is the sum of the Q at each frequency. Apparent power S = V·I no longer squares with P and Q: distortion power D appears, with S² = P² + Q² + D². That is why the power factor P/S can be lower than the cos φ at any single frequency.
Three-phase
Generator: you enter the line voltage; in star, each phase is U/√3. Phase A has the phase you write, with B and C 120° behind and ahead; in negative sequence, the other way round. If its N is joined to nothing, it stays isolated.
Harmonics: each generator component is shared out according to its order relative to the first frequency. The third harmonic comes out equal in all three phases: it adds up in the neutral and, with no neutral, does not flow.
Load: in star or delta, equal or different per phase. In star, if you leave N unconnected, the centre floats and you see its displacement.
Motor and capacitors: they become impedances from their data, at the stated voltage and frequency. A real motor is not a fixed impedance, but for the steady-state power split it is usually enough.
Two wattmeters: each block gives the readings W1 (U AC, I A) and W2 (U BC, I B). Their sum is the total power if no current flows in the neutral.
Conventions
AC values are RMS and the phase is on cosine: v(t) = √2·V·cos(2πft + φ).
A voltage source has + at its first terminal, on the left when not rotated. The current of each element goes from its first terminal to its second.
Negative P means that element delivers power. A load absorbs; a source usually delivers.
If the diagram has no ground, voltages are given relative to one of its nodes.
In an impedance Z, X is the reactance at the stated frequency: positive behaves as an inductor and negative as a capacitor, at the other frequencies too.
Limits. This is linear steady state: it does not work out starting or transients, or take saturation or nonlinear elements into account. A resistance has the same value at all frequencies: skin effect is not included. Always check that the results make sense before using them on a real installation.