Extension and compensating cables according to IEC 60584-3 and the former national standards
Choose the thermocouple type to see what its cable looks like in each standard. Since 1989 the international standard IEC 60584-3 has unified the colours in Europe, but older installations and imported equipment still use national codes, and the same colour can mean different things: green is type K in IEC, but platinum (R/S) in ANSI and BS.
Each swatch shows sheath · positive conductor · negative conductor. Hover over it to see the names.
| Letter | Meaning | Example |
|---|---|---|
| X | Extension cable: same alloys as the thermocouple. The most accurate, but also the most expensive. | KX, JX, TX, EX, NX |
| C | Compensating cable: different, cheaper alloys that match the thermocouple EMF only over a short temperature range (usually 0 to 100 or 200 °C). | KC, NC, RC, SC, BC |
| A / B | Compensating variants with different alloys. A usually has the better tolerance; B, the wider temperature range. | KCA (iron/constantan), KCB (copper/constantan), RCA, RCB, SCA, SCB |
Platinum thermocouples (R, S and B) almost always use copper and copper-nickel compensating cable, because extension cable would cost as much as the sensor itself. Base metal types mainly use extension cable.
| Cable | Class 1 | Class 2 | Cable range | Measuring junction temp. |
|---|---|---|---|---|
| KX | ±60 µV (±1.5 °C) | ±100 µV (±2.5 °C) | −25 to 200 °C | 900 °C |
| KCA | – | ±100 µV (±2.5 °C) | 0 to 150 °C | 900 °C |
| KCB | – | ±100 µV (±2.5 °C) | 0 to 100 °C | 900 °C |
| JX | ±85 µV (±1.5 °C) | ±140 µV (±2.5 °C) | −25 to 200 °C | 500 °C |
| TX | ±30 µV (±0.5 °C) | ±60 µV (±1.0 °C) | −25 to 100 °C | 300 °C |
| EX | ±120 µV (±1.5 °C) | ±200 µV (±2.5 °C) | −25 to 200 °C | 500 °C |
| NX | ±60 µV (±1.5 °C) | ±100 µV (±2.5 °C) | −25 to 200 °C | 900 °C |
| NC | – | ±100 µV (±2.5 °C) | 0 to 150 °C | 900 °C |
| RCA / SCA | – | ±30 µV (±2.5 °C) | 0 to 100 °C | 1000 °C |
| RCB / SCB | – | ±60 µV (±5.0 °C) | 0 to 200 °C | 1000 °C |
| BC | – | ±40 µV (±3.5 °C) | 0 to 100 °C | 1400 °C |
The tolerance is the error added by the cable when its ends are at different temperatures within its range. Outside that range, especially with compensating cables, the error grows quickly: do not run them close to furnaces or hot pipes.
Thermocouple wires are often specified by American (AWG) or British (SWG) gauge. The higher the number, the thinner the wire.