Thermocouple cable colours

Extension and compensating cables according to IEC 60584-3 and the former national standards

Identify a thermocouple cable

Choose the thermocouple type to see what its cable looks like in each standard. Since 1989 the international standard IEC 60584-3 has unified the colours in Europe, but older installations and imported equipment still use national codes, and the same colour can mean different things: green is type K in IEC, but platinum (R/S) in ANSI and BS.

Full colour table

Each swatch shows sheath · positive conductor · negative conductor. Hover over it to see the names.

Extension or compensating: what the letters mean

LetterMeaningExample
XExtension cable: same alloys as the thermocouple. The most accurate, but also the most expensive.KX, JX, TX, EX, NX
CCompensating cable: different, cheaper alloys that match the thermocouple EMF only over a short temperature range (usually 0 to 100 or 200 °C).KC, NC, RC, SC, BC
A / BCompensating variants with different alloys. A usually has the better tolerance; B, the wider temperature range.KCA (iron/constantan), KCB (copper/constantan), RCA, RCB, SCA, SCB

Platinum thermocouples (R, S and B) almost always use copper and copper-nickel compensating cable, because extension cable would cost as much as the sensor itself. Base metal types mainly use extension cable.

Cable tolerances (IEC 60584-3)

CableClass 1Class 2Cable rangeMeasuring junction temp.
KX±60 µV (±1.5 °C)±100 µV (±2.5 °C)−25 to 200 °C900 °C
KCA–±100 µV (±2.5 °C)0 to 150 °C900 °C
KCB–±100 µV (±2.5 °C)0 to 100 °C900 °C
JX±85 µV (±1.5 °C)±140 µV (±2.5 °C)−25 to 200 °C500 °C
TX±30 µV (±0.5 °C)±60 µV (±1.0 °C)−25 to 100 °C300 °C
EX±120 µV (±1.5 °C)±200 µV (±2.5 °C)−25 to 200 °C500 °C
NX±60 µV (±1.5 °C)±100 µV (±2.5 °C)−25 to 200 °C900 °C
NC–±100 µV (±2.5 °C)0 to 150 °C900 °C
RCA / SCA–±30 µV (±2.5 °C)0 to 100 °C1000 °C
RCB / SCB–±60 µV (±5.0 °C)0 to 200 °C1000 °C
BC–±40 µV (±3.5 °C)0 to 100 °C1400 °C

The tolerance is the error added by the cable when its ends are at different temperatures within its range. Outside that range, especially with compensating cables, the error grows quickly: do not run them close to furnaces or hot pipes.

Good wiring practice

AWG and SWG gauges

Thermocouple wires are often specified by American (AWG) or British (SWG) gauge. The higher the number, the thinner the wire.