Resistance thermometers: ohms ↔ temperature according to IEC 60751, tolerances, lead error and tables
Calculates how much the connecting wires and the measuring current distort the reading, at the temperature entered above.
A resistance thermometer (RTD, Resistance Temperature Detector) relies on the fact that the resistance of a pure metal increases with temperature. Platinum is the reference material: it is stable, almost linear and does not oxidise. Pt100 means "platinum, 100 Ω at 0 °C"; the Pt1000 is 1000 Ω, gives ten times more signal and is less sensitive to lead resistance.
The resistance–temperature relationship of industrial platinum is defined by IEC 60751 with the Callendar-Van Dusen equation:
with \(A = 3.9083\cdot10^{-3}\ °C^{-1}\), \(B = -5.775\cdot10^{-7}\ °C^{-2}\) and \(C = -4.183\cdot10^{-12}\ °C^{-4}\). The mean coefficient between 0 and 100 °C, \(\alpha = \frac{R_{100} - R_0}{100\,R_0} = 0.00385\ °C^{-1}\), identifies this platinum. Some old American sensors use α = 0.00392: their tables are different and must not be mixed up.
| Material | Usual range | Special range | Characteristics |
|---|---|---|---|
| Platinum (Pt100, Pt1000) | −200 to 600 °C | up to 850 °C | Stable, interchangeable and standardised. The most widely used. |
| Nickel (Ni100, Ni1000) | −60 to 180 °C | up to 350 °C | More sensitive and cheaper, not very linear. HVAC. |
| Copper (Cu10, Cu100) | −100 to 100 °C | up to 150 °C | Very linear but low resistance. Motor and transformer windings. |
| NTC/PTC thermistors | −100 to 200 °C | – | Very sensitive and very non-linear; thermal and electronic protection. |
| Class | Tolerance | Range, wire-wound element | Range, film element | At 0 °C (Pt100) |
|---|---|---|---|---|
| AA (1/3 DIN) | ±(0.10 + 0.0017·|t|) °C | −50 to 250 °C | 0 to 150 °C | ±0.10 °C · ±0.04 Ω |
| A | ±(0.15 + 0.002·|t|) °C | −100 to 450 °C | −30 to 300 °C | ±0.15 °C · ±0.06 Ω |
| B | ±(0.30 + 0.005·|t|) °C | −196 to 600 °C | −50 to 500 °C | ±0.30 °C · ±0.12 Ω |
| C | ±(0.6 + 0.01·|t|) °C | −196 to 600 °C | −50 to 600 °C | ±0.6 °C · ±0.23 Ω |
The calculator applies the ranges of wire-wound elements. Class AA used to be called "1/3 DIN"; sensors of 1/5 and 1/10 DIN, outside the standard, are also sold.
To measure the resistance a current has to flow, which dissipates \(P = I^2 R\) and heats the sensor above the medium. The error is \(\Delta t = P / \delta\), where \(\delta\) is the dissipation constant (mW/°C) given by the manufacturer: a few mW/°C in still air and considerably more in a stirred liquid. With 1 mA in a Pt100 the power is 0.1 mW and the error is usually negligible; with 5 mA it is already 25 times greater.
| Criterion | Thermocouple | Pt100 |
|---|---|---|
| Accuracy and stability | Medium (±1.5 to ±2.5 °C) | High (±0.1 to ±0.3 °C at 0 °C) |
| Range | −200 to 1800 °C | −200 to 850 °C |
| Size and speed | Can be very thin and fast | Larger element, slower response |
| Vibration resistance | Very good | Fair |
| Wiring | Extension or compensating cable | Ordinary copper cable |
| Cold junction | Needs compensation | Not applicable |
| Cost | Low | 2 to 3 times higher |
Related: thermocouple calculator, thermocouple guide, 4–20 mA transmitters and Ohm's law.