Signal scaling, NAMUR NE43 levels and loop supply check
Define the transmitter range and type in any of the three boxes: the others update.
A 2-wire transmitter needs a minimum voltage at its terminals to work. Whatever is left from the supply is shared between the input resistance of the instrument, the cable and any barriers. At the maximum loop current, everything must fit within the supply voltage.
The NAMUR NE43 recommendation reserves currents outside the range to signal faults, so that the control system knows whether the measurement can be trusted:
| Current | Meaning |
|---|---|
| ≤ 3.6 mA | Transmitter or sensor failure (low alarm) |
| 3.6 to 3.8 mA | Measurement below range (low saturation) |
| 3.8 to 20.5 mA | Valid measurement (including a small margin above and below the range) |
| 20.5 to 21 mA | Measurement above range (high saturation) |
| ≥ 21 mA | Transmitter or sensor failure (high alarm) |
In temperature transmitters you configure whether a broken probe should drive the output to high or low alarm. In a furnace the high alarm (≥ 21 mA) is preferable: the control interprets it as over-temperature and cuts the heating.
To read the current with a voltage input, a 250 Ω resistor is enough: 4–20 mA becomes 1–5 V. That same value, as a minimum, is what devices with the HART protocol need; HART superimposes a 1200/2200 Hz digital signal on the 4–20 mA to configure and diagnose the transmitter without interrupting the measurement.
A transmitter in the probe head converts the millivolts of the thermocouple or the ohms of the Pt100 into 4–20 mA right where the measurement is taken. The cable to the control system can then be ordinary copper instead of compensating cable, the cold junction is compensated in the head itself and the signal travels hundreds of metres without losing accuracy. Digital models also linearise the sensor curve, detect a broken probe and accept any type of thermocouple or resistance thermometer.