EN

Field in capacitors and cables

How the field is shared in an insulator, why an air void is dangerous and why medium-voltage cables have a screen

Insulation does not fail because of the voltage it withstands, but because of the electric field, in kV/mm, at its most stressed point. If the field is shared evenly, you simply divide the voltage by the thickness. But when there are several layers of different materials or the geometry is curved, as in a cable, some areas work much harder than others.

One- or two-layer parallel-plate capacitor

With a single dielectric, the field is uniform: \( E = U/d \). With two layers in series, the electric flux density D is the same in both, so the field is greater in the one with the lower permittivity:

\[ E_i = \frac{U}{\varepsilon_{ri} \sum_j d_j/\varepsilon_{rj}} \qquad C = \frac{\varepsilon_0\,A}{\sum_j d_j/\varepsilon_{rj}} \]

The lines are denser where the field is greater; in red, the layer that exceeds its approximate dielectric strength.

The air void

Air has the lowest permittivity of all insulators and the poorest dielectric strength. A bubble inside a resin, a gap between the insulation and the steel, or a layer of air between the paper and the conductor carry a field several times higher than the surrounding solid. With the simulator's initial settings, 10 kV across 2 mm of paper and 0.2 mm of air leaves the paper at a comfortable 3.7 kV/mm, but the air at almost 13 kV/mm, far above what it can withstand.

That is where partial discharges appear: small sparks inside the void that do not bridge the whole insulation but slowly erode it until it fails. That is why medium-voltage windings are vacuum-impregnated, dry-type transformers are cast without bubbles and cable joints are made with care.

Screened medium-voltage cable

In a single-core screened cable, the field runs radially from the conductor to the screen. Since the area is smaller near the conductor, the field is highest next to it and lowest next to the screen:

\[ E(r) = \frac{U_0}{r\,\ln(R/r_0)} \qquad C = \frac{2\pi\,\varepsilon_0\,\varepsilon_r}{\ln(R/r_0)} \]

U0 is the voltage between conductor and screen, the phase-to-earth voltage of the network; r0 is the radius over the conductor's semiconducting layer and R the radius under the outer semiconducting layer.

Field in the insulationField if it were uniform, U0/thickness

Approximate dimensions of commercial cables; see the manufacturer's data sheet for exact values. The charging current is at 50 Hz.

What it shows

Testing and precautions

To see how the field is drawn around charges, points and plates, use the electric field simulator. For circuit capacitors, the capacitor calculator.