Short-circuit current and breaking capacity

From the transformer or battery to the fault point, and whether the chosen device can withstand it

1. Calculator

Installation
V
MVA
kVA
%
W
mm²
mΩ/m
Cable to the fault point
mm²
m
Protective device
A
kA
%

How to use it

  1. Choose AC or DC and enter the source data from its nameplate.
  2. Enter the cable up to the point you want to check. With length 0 you get the current at the transformer or battery terminals.
  3. Choose the device and enter its breaking capacity at the service voltage, from the catalogue.
  4. Read the checks. Also try the furthest end: there the minimum current must still trip the protection.

Impedance method

\[ Z_T = \frac{u_{cc}}{100}\frac{U_n^2}{S_n} \qquad R_T = P_{cc}\frac{U_n^2}{S_n^2} \qquad X_T = \sqrt{Z_T^2 - R_T^2} \]
\[ I_{k3} = \frac{c\,U_n}{\sqrt{3}\,\left|Z\right|} \qquad I_{k2} = \frac{\sqrt{3}}{2}I_{k3} \qquad i_p = \kappa\sqrt{2}\,I_{k3} \]
\[ t_{adm} = \left(\frac{k\,S}{I}\right)^2 \]

The network, transformer and cable are added in series, all referred to low voltage. c = 1.05 is used for the maximum current and c = 0.95 with a hot cable (1.5 times its resistance at 20 °C) for the minimum. The phase-to-neutral case assumes a delta-star transformer. The tadm formula is heating without dissipation, valid up to about 5 s.

Which current each check uses

CurrentWhat it is for
Ik3, the maximumDevice breaking capacity (Icu or Icn).
ip, the peakMaking capacity Icm and forces on busbars.
Minimum Ik1Magnetic tripping at the end of the line.
I²t during the faultKeeping the cable below its temperature limit.

In direct current

The current comes from U/R, adding the internal resistance and the go-and-return resistance of the cable. L/R also matters: a nearby battery gives a very short τ, while a long line, a coil or a motor lengthens it. If τ exceeds the L/R at which the device was tested, its declared breaking capacity no longer applies. The 15 ms value is only a common starting point: use the catalogue figure.

Data sources and limits

The formulas follow the idea of IEC 60909 without its correction factors, such as the transformer impedance factor. The ratio n of Icm/Icu is quoted from IEC 60947-2; the Ics of modular devices, from EN 60898; and the k values, from IEC 60364-4-43. They are written according to these standards without checking against the official text, so verify them before using them in a project. Motor contribution is not included. In Spain, the REBT guide also allows a simplified estimate, I = 0.8·U/R. This calculation gives guidance, but it does not replace a design by a competent engineer.