From the transformer or battery to the fault point, and whether the chosen device can withstand it
The network, transformer and cable are added in series, all referred to low voltage. c = 1.05 is used for the maximum current and c = 0.95 with a hot cable (1.5 times its resistance at 20 °C) for the minimum. The phase-to-neutral case assumes a delta-star transformer. The tadm formula is heating without dissipation, valid up to about 5 s.
| Current | What it is for |
|---|---|
| Ik3, the maximum | Device breaking capacity (Icu or Icn). |
| ip, the peak | Making capacity Icm and forces on busbars. |
| Minimum Ik1 | Magnetic tripping at the end of the line. |
| I²t during the fault | Keeping the cable below its temperature limit. |
The current comes from U/R, adding the internal resistance and the go-and-return resistance of the cable. L/R also matters: a nearby battery gives a very short τ, while a long line, a coil or a motor lengthens it. If τ exceeds the L/R at which the device was tested, its declared breaking capacity no longer applies. The 15 ms value is only a common starting point: use the catalogue figure.
The formulas follow the idea of IEC 60909 without its correction factors, such as the transformer impedance factor. The ratio n of Icm/Icu is quoted from IEC 60947-2; the Ics of modular devices, from EN 60898; and the k values, from IEC 60364-4-43. They are written according to these standards without checking against the official text, so verify them before using them in a project. Motor contribution is not included. In Spain, the REBT guide also allows a simplified estimate, I = 0.8·U/R. This calculation gives guidance, but it does not replace a design by a competent engineer.
See also: Breaking capacity and opening, Protection curves, Short-circuit transient and Voltage drop.