Typical technical data for 8-pole three-phase squirrel-cage induction motors (750 rpm synchronous speed at 50 Hz), from 0.18 kW to 250 kW: speed, efficiency, power factor, current, torques, starting current, moment of inertia and weight.
How many rpm does a 8-pole motor run at? Its synchronous speed is 750 rpm at 50 Hz and 900 rpm at 60 Hz (n = 120 · f / poles). On load it runs a little slower because of slip: from the table, 650 to 740 rpm at 50 Hz, about 720 rpm for medium sizes, and about 865 rpm at 60 Hz.
| Power | Full-load characteristics | Rated torque | Starting torque | Breakdown torque | Starting I | Moment of inertia | Weight | ||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| kW | hp | rpm | Efficiency (%) | cos φ | A a 380 V | Nm | Nm | Nm | A | kg·m² | kg |
| 0.18 | 0.25 | 650 | 55 | 0.67 | 0.75 | 2.6 | 4.2 | 5.3 | 1.8 | 0.0018 | 12 |
| 0.25 | 0.34 | 670 | 55 | 0.67 | 1.05 | 3.6 | 5.7 | 7.5 | 2.6 | 0.0021 | 13 |
| 0.37 | 0.5 | 680 | 60 | 0.7 | 1.36 | 5.2 | 8.3 | 10 | 3.5 | 0.0032 | 20 |
| 0.55 | 0.75 | 680 | 62 | 0.7 | 2 | 7.7 | 12 | 16 | 5.4 | 0.0039 | 21 |
| 0.75 | 1 | 690 | 68 | 0.74 | 2.3 | 10 | 19 | 23 | 8.0 | 0.0075 | 29 |
| 1.1 | 1.5 | 700 | 70 | 0.74 | 3.3 | 15 | 27 | 33 | 13 | 0.011 | 33 |
| 1.5 | 2 | 705 | 75 | 0.75 | 4 | 20 | 37 | 47 | 16 | 0.018 | 43 |
| 2.2 | 3 | 705 | 77 | 0.76 | 5.7 | 30 | 60 | 69 | 26 | 0.035 | 57 |
| 3 | 4 | 710 | 78 | 0.76 | 7.7 | 40 | 81 | 93 | 38 | 0.04 | 66 |
| 4 | 5.5 | 715 | 83 | 0.76 | 9.7 | 53 | 112 | 120 | 44 | 0.062 | 97 |
| 5.5 | 7.5 | 715 | 84 | 0.76 | 13.5 | 73 | 162 | 180 | 68 | 0.082 | 115 |
| 7.5 | 10 | 715 | 85 | 0.77 | 17.5 | 100 | 230 | 270 | 88 | 0.1 | 135 |
| 11 | 15 | 725 | 87 | 0.77 | 25 | 145 | 290 | 330 | 130 | 0.18 | 176 |
| 15 | 20 | 725 | 89 | 0.8 | 32 | 198 | 430 | 510 | 160 | 0.34 | 275 |
| 18.5 | 25 | 730 | 90 | 0.81 | 38.5 | 240 | 520 | 570 | 192 | 0.53 | 310 |
| 22 | 30 | 730 | 91 | 0.81 | 45 | 290 | 630 | 690 | 238 | 0.63 | 350 |
| 30 | 40 | 730 | 91.5 | 0.83 | 61 | 390 | 850 | 930 | 305 | 1 | 460 |
| 37 | 50 | 735 | 91.5 | 0.84 | 73.5 | 480 | 960 | 1100 | 441 | 1.7 | 630 |
| 45 | 60 | 735 | 92 | 0.84 | 90 | 580 | 1160 | 1300 | 558 | 2 | 720 |
| 55 | 75 | 735 | 92.5 | 0.85 | 106 | 710 | 1400 | 1600 | 636 | 3.8 | 830 |
| 75 | 100 | 735 | 93 | 0.85 | 145 | 970 | 1900 | 2200 | 870 | 4.2 | 960 |
| 90 | 125 | 740 | 93.5 | 0.86 | 170 | 1160 | 2070 | 2500 | 1054 | 4.7 | 1100 |
| 110 | 150 | 740 | 93.5 | 0.86 | 207 | 1400 | 2500 | 3000 | 1242 | 5.1 | 1200 |
| 132 | 180 | 740 | 94 | 0.86 | 249 | 1700 | 2700 | 3400 | 1444 | 9 | 1550 |
| 160 | 220 | 740 | 94 | 0.86 | 302 | 2060 | 3250 | 4100 | 1812 | 10.5 | 1750 |
| 200 | 270 | 740 | 95 | 0.87 | 368 | 2570 | 4100 | 5100 | 2208 | 17 | 2100 |
| 250 | 340 | 740 | 95 | 0.87 | 462 | 3200 | 5100 | 6400 | 2772 | 21 | 2550 |
On mobile, swipe the table sideways to see all the columns.
| Column | Meaning |
|---|---|
| kW / hp | Useful mechanical power at the shaft. 1 hp (metric) = 0.736 kW. |
| rpm | Actual full-load speed. It is slightly lower than the synchronous speed (750 rpm at 50 Hz) because of slip. |
| Efficiency | Ratio between the mechanical power delivered and the electrical power drawn. |
| cos φ | Full-load power factor. It shows how much reactive energy the motor draws. |
| A a 380 V | Rated current per phase with a 380 V three-phase supply. |
| Rated torque | Shaft torque at full load and rated speed. |
| Starting torque | Torque delivered by the motor at standstill when switched on. It must exceed the load torque. |
| Breakdown torque | Highest torque the motor can deliver before it stalls. |
| Starting I | Current peak during direct-on-line starting, usually 5 to 8 times the rated current. |
| Moment of inertia | Rotor inertia. Used to calculate starting and braking times. |
| Weight | Approximate weight of the motor with a standard frame. |
Rated torque from power and speed:
Rated current of a three-phase motor:
Current at another voltage (for example, 400 V instead of 380 V):
Slip:
A 7.5 kW, 715 rpm motor has a rated torque of 9550 · 7.5 / 715 ≈ 100 Nm, the value in the table. That is about four times the torque of a 2-pole motor of the same power, because it runs at a quarter of its speed. At 380 V it draws about 17.5 A; at 400 V it would be about 16.6 A. Note also its cos φ of 0.77: lower than in faster motors, so power factor correction is usually worthwhile.
8-pole motors run at about 700–740 rpm. They are used in machines that need very low speed and high shaft torque: large-diameter fans and extractors, agitators, mills, crushers, piston pumps or direct drives without a gearbox. They are the largest and heaviest for a given power, and at low ratings their power factor and efficiency are lower than those of 2 or 4-pole motors.
Typical approximate values for general-purpose motors. Each manufacturer and series (IE1, IE2, IE3…) has its own data: always check the nameplate and the manufacturer's catalogue.