Typical technical data for 2-pole three-phase squirrel-cage induction motors (3000 rpm synchronous speed at 50 Hz), from 0.18 kW to 250 kW: speed, efficiency, power factor, current, torques, starting current, moment of inertia and weight.
How many rpm does a 2-pole motor run at? Its synchronous speed is 3000 rpm at 50 Hz and 3600 rpm at 60 Hz (n = 120 · f / poles). On load it runs a little slower because of slip: from the table, 2740 to 2980 rpm at 50 Hz, about 2900 rpm for medium sizes, and about 3480 rpm at 60 Hz.
| Power | Full-load characteristics | Rated torque | Starting torque | Breakdown torque | Starting I | Moment of inertia | Weight | ||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| kW | hp | rpm | Efficiency (%) | cos φ | A a 380 V | Nm | Nm | Nm | A | kg·m² | kg |
| 0.18 | 0.25 | 2740 | 60 | 0.79 | 0.58 | 0.63 | 1.44 | 1.67 | 2.3 | 0.00017 | 5.5 |
| 0.25 | 0.34 | 2765 | 64 | 0.8 | 0.72 | 0.86 | 1.99 | 2.30 | 3.1 | 0.00024 | 7 |
| 0.37 | 0.5 | 2765 | 66 | 0.8 | 1.06 | 1.28 | 2.94 | 3.40 | 4.6 | 0.0004 | 8 |
| 0.55 | 0.75 | 2800 | 70 | 0.82 | 1.46 | 1.88 | 4.31 | 4.99 | 7.0 | 0.0006 | 9 |
| 0.75 | 1 | 2850 | 75 | 0.83 | 1.85 | 2.51 | 5.78 | 6.69 | 9.3 | 0.00082 | 12 |
| 1.1 | 1.5 | 2850 | 76 | 0.85 | 2.6 | 3.69 | 8.48 | 9.8 | 14 | 0.0012 | 13 |
| 1.5 | 2 | 2855 | 78 | 0.88 | 3.3 | 5.02 | 11.5 | 13.3 | 20 | 0.0017 | 18 |
| 2.2 | 3 | 2860 | 79 | 0.88 | 4.8 | 7.35 | 16.9 | 19.5 | 32 | 0.0023 | 22 |
| 3 | 4 | 2895 | 82 | 0.88 | 6.2 | 9.90 | 22.8 | 26.3 | 42 | 0.004 | 31 |
| 4 | 5.5 | 2895 | 84.5 | 0.88 | 8.2 | 13.2 | 30.3 | 35.1 | 57 | 0.0065 | 37 |
| 5.5 | 7.5 | 2925 | 85 | 0.88 | 11 | 18.0 | 41.3 | 47.8 | 75 | 0.014 | 55 |
| 7.5 | 10 | 2930 | 85.5 | 0.88 | 15 | 24.4 | 56.2 | 65.0 | 105 | 0.019 | 60 |
| 11 | 15 | 2930 | 87 | 0.88 | 22 | 35.9 | 82.5 | 95.4 | 150 | 0.035 | 110 |
| 15 | 20 | 2935 | 87 | 0.88 | 30 | 48.8 | 112 | 130 | 210 | 0.042 | 123 |
| 18.5 | 25 | 2935 | 89 | 0.88 | 36 | 60.2 | 138 | 160 | 270 | 0.065 | 138 |
| 22 | 30 | 2940 | 89 | 0.89 | 43 | 71.5 | 164 | 190 | 301 | 0.08 | 185 |
| 30 | 40 | 2950 | 89 | 0.9 | 56 | 97.1 | 223 | 258 | 392 | 0.12 | 232 |
| 37 | 50 | 2950 | 89 | 0.9 | 70 | 120 | 275 | 319 | 490 | 0.17 | 260 |
| 45 | 60 | 2960 | 90 | 0.9 | 83 | 145 | 334 | 386 | 581 | 0.23 | 320 |
| 55 | 75 | 2965 | 90.5 | 0.9 | 103 | 177 | 407 | 471 | 700 | 0.5 | 415 |
| 75 | 100 | 2970 | 91.5 | 0.9 | 136 | 241 | 555 | 641 | 952 | 0.75 | 570 |
| 90 | 125 | 2970 | 92 | 0.9 | 168 | 289 | 666 | 770 | 1170 | 0.85 | 650 |
| 110 | 150 | 2975 | 92 | 0.9 | 203 | 353 | 812 | 939 | 1420 | 1.6 | 880 |
| 132 | 180 | 2975 | 92.5 | 0.9 | 241 | 424 | 975 | 1127 | 1680 | 1.9 | 970 |
| 160 | 220 | 2975 | 93 | 0.91 | 280 | 514 | 1181 | 1366 | 1960 | 2.3 | 1200 |
| 200 | 270 | 2980 | 94 | 0.91 | 356 | 641 | 1474 | 1705 | 2420 | 3.8 | 1400 |
| 250 | 340 | 2980 | 94 | 0.91 | 445 | 801 | 1843 | 1760 | 3020 | 4.8 | 1650 |
On mobile, swipe the table sideways to see all the columns.
| Column | Meaning |
|---|---|
| kW / hp | Useful mechanical power at the shaft. 1 hp (metric) = 0.736 kW. |
| rpm | Actual full-load speed. It is slightly lower than the synchronous speed (3000 rpm at 50 Hz) because of slip. |
| Efficiency | Ratio between the mechanical power delivered and the electrical power drawn. |
| cos φ | Full-load power factor. It shows how much reactive energy the motor draws. |
| A a 380 V | Rated current per phase with a 380 V three-phase supply. |
| Rated torque | Shaft torque at full load and rated speed. |
| Starting torque | Torque delivered by the motor at standstill when switched on. It must exceed the load torque. |
| Breakdown torque | Highest torque the motor can deliver before it stalls. |
| Starting I | Current peak during direct-on-line starting, usually 5 to 8 times the rated current. |
| Moment of inertia | Rotor inertia. Used to calculate starting and braking times. |
| Weight | Approximate weight of the motor with a standard frame. |
Rated torque from power and speed:
Rated current of a three-phase motor:
Current at another voltage (for example, 400 V instead of 380 V):
Slip:
A 7.5 kW, 2930 rpm motor has a rated torque of 9550 · 7.5 / 2930 ≈ 24.4 Nm, the value in the table. At 380 V it draws about 15 A; at 400 V it would be about 14.3 A. On direct-on-line starting it will draw around 105 A, about 7 times the rated current. Bear this in mind when choosing the protection and consider star-delta starting or a soft starter.
2-pole motors are the fastest on a 50 Hz supply. They are common in centrifugal pumps, fans, compressors, blowers and machine tools that need high speeds. For the same power they deliver less torque than a 4, 6 or 8-pole motor, but they are smaller and lighter.
Typical approximate values for general-purpose motors. Each manufacturer and series (IE1, IE2, IE3…) has its own data: always check the nameplate and the manufacturer's catalogue.